Event ID
Description
7: Not Connected
8: Unknown
DatID: Not user relevant
0xEA04
SBUS: Multiple configuration of a periphery address
ZINFO1: Periphery address
ZINFO2: Slot
ZINFO3: Data width
0xEA05
Internal error - Please contact the hotline!
0xEA07
Internal error - Please contact the hotline!
0xEA08
SBUS: Configured input data width not the same as the connected input data width
ZINFO1: Configured input data width
ZINFO2: Slot
ZINFO3: Input data width of the connected component
0xEA09
SBUS: Configured output data width not the same as the connected output data width
ZINFO1: Configured output data width
ZINFO2: Slot
ZINFO3: Output data width of the plugged component
0xEA10
SBUS: Input periphery address outside the periphery area
ZINFO1: Periphery address
ZINFO2: Slot
ZINFO3: Data width
0xEA11
SBUS: Output periphery address outside the periphery area
ZINFO1: Periphery address
ZINFO2: Slot
ZINFO3: Data width
0xEA12
SBUS: Error in writing dataset
ZINFO1: Slot
ZINFO2: Dataset number
ZINFO3: Dataset length
0xEA14
SBUS: Multiple configuration of a periphery address (diagnostic address)
ZINFO1: Periphery address
ZINFO2: Slot
ZINFO3: Data width
0xEA15
Internal error - Please contact the hotline!
ZINFO2: Slot of the master
0xEA18
SBUS: Error in mapping the master periphery
ZINFO2: Slot of the master
0xEA19
Internal error - Please contact the hotline!
System 300S
+
System specific event IDs
HB140 | CPU | 315-4PN23 | en | 18-02
175