The PROFIBUS line has to be terminated with its ripple resistor. Please
make sure to terminate the last participants on the bus at both ends by
activating the terminating resistor.
In PROFIBUS all participants are wired parallel. For that purpose, the bus cable must be
feed-through. Via the order number 972-0DP10 you may order the bus connector "Easy-
Conn" from Yaskawa. This is a bus connector with switchable terminating resistor and
integrated bus diagnostic.
Dimensions in mm
0°
45°
90°
A
64
61
66
B
34
53
40
C
15.8
15.8
15.8
To connect this EasyConn plug, please use the standard PROFIBUS
cable type A (EN50170). Starting with release 5 you also can use highly
flexible bus cable:
Lapp cable order no: 2170222, 2170822, 2170322.
With the order no. 905-6AA00 Yaskawa offers the "EasyStrip" de-isolating
tool that makes the connection of the EasyConn much easier.
Dimensions in mm
The "EasyConn" bus connector is provided with a switch that is used to activate a termi-
nating resistor.
EasyConn bus connector
Termination with "Easy-
Conn"
System 300S
+
Deployment PROFIBUS communication
PROFIBUS installation guidelines
HB140 | CPU | 315-4PN23 | en | 18-02
97