9.11.1
Replace device
For the replacement the "replace device" must be in "delivery state". If you have not
received a new "replace device" from VIPA, you have to prepare this with the following
approach:
1.
For this connect your "replace device" local at your PG.
2.
Start the Siemens SIMATIC Manager and execute
‘PLC
è
Edit Ethernet node’
3.
Click at
‘Nodes accessible online’
at [Browse].
4.
Select the according IO device, which you identify as your "replace device".
5.
Click at
‘Reset to factory settings’
at [Reset].
ð
Your IO device is now reset and has then "delivery state".
For the replacement the "replace device" must be in "delivery state".
1.
Disconnect if not already done your device to be exchanged from power.
2.
Replace this by your "replace device".
3.
Connect the "replaced device" to power and turn it ON.
ð
Here by comparison of target and current topology, the "replaced device" is
automatically detected by the IO controller and automatically integrated to the
user data traffic.
Prepare the replace device
Replace device
System 300S
+
Deployment Ethernet communication - PROFINET
Device replacement without exchangeable medium/PG > Replace device
HB140 | CPU | 315-4PN23 | en | 18-02
134