Mounting conditions
Mounting place
-
In the control cabinet
Mounting position
-
Horizontal and vertical
EMC
Standard
Comment
Emitted interference
EN 61000-6-4
Class A (Industrial area)
Noise immunity
zone B
EN 61000-6-2
Industrial area
EN 61000-4-2
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity 2)
EN 61000-4-3
HF field immunity (casing)
80MHz … 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
EN 61000-4-6
HF conducted
150kHz … 80MHz, 10V, 80% AM (1kHz)
EN 61000-4-4
Burst, degree of severity 3
EN 61000-4-5
Surge, degree of severity 3 *
*)
Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection
elements like conductors for lightning and overvoltage is necessary.
VIPA System 300S
+
Basics
General data
HB140 | CPU-SC | 313-5BF23 | en | 19-01
17