9.6 TIA Portal - Project transfer
There are the following possibilities for project transfer into the CPU:
n
Transfer via MPI
n
Transfer via Ethernet
n
Transfer via memory card
Currently the VIPA programming cables for transfer via MPI are not supported. This is
only possible with the programming cable from Siemens.
1.
Establish a connection to the CPU via MPI with an appropriate programming cable.
Information may be found in the corresponding documentation of the programming
cable.
2.
Switch-ON the power supply of your CPU and start the Siemens TIA Portal with
your project.
3.
Select in the
Project tree
your CPU and choose
‘Context menu
è
Download to device
è
Hardware configuration’
to transfer the hardware configu-
ration.
4.
To transfer the PLC program choose
‘Context menu
è
Download to device
è
Software’
. Due to the system you have to transfer hardware configuration and
PLC program separately.
For transfer via Ethernet the CPU has the following interface:
n
X5: Ethernet PG/OP channel
So that you may the according Ethernet interface, you have to assign IP address parame-
ters by means of the "initialization".
Please consider to use the same IP address data in your project for the CP 343-1.
1.
For the transfer, connect, if not already done, the appropriate Ethernet jack to your
Ethernet.
2.
Open your project with the Siemens TIA Portal.
3.
Click in the
Project tree
at
Online access
and choose here by a double-click your
network card, which is connected to the Ethernet PG/OP interface.
4.
Select in the
Project tree
your CPU and click at [Go online].
5.
Set the access path by selecting "PN/IE" as type of interface, your network card and
the according subnet. Then a net scan is established and the corresponding station
is listed.
6.
Establish with [Connect] a connection.
7.
Click to
‘Online
è
Download to device’
.
ð
The according block is compiled and by a request transferred to the target
device. Provided that no new hardware configuration is transferred to the CPU,
the entered Ethernet connection is permanently stored in the project as transfer
channel.
Overview
Transfer via MPI
Transfer via Ethernet
Initialization
Transfer
VIPA System 300S
+
Configuration with TIA Portal
TIA Portal - Project transfer
HB140 | CPU-SC | 313-5BF23 | en | 19-01
188