Event ID
Description
ZINFO3: Not user relevant
DatID: Not user relevant
0xE705
Too many PROFIBUS slaves configured
ZINFO1: Diagnostic address of the PROFIBUS master
ZINFO2: Number of configured slaves
ZINFO3: Number of admissible slaves
0xE710
On-board PROFIBUS/MPI: Bus error occurred
PK: Not user relevant
ZINFO1: Interface
ZINFO2: Not user relevant
ZINFO3: Not user relevant
DatID: Not user relevant
0xE720
Internal error - Please contact the hotline!
ZINFO1: Slave no
ZINFO2: Not user relevant
ZINFO3: Not user relevant
DatID: Master system ID
0xE721
Internal error - Please contact the hotline!
ZINFO1: Not user relevant
ZINFO2: Master system ID
ZINFO3: Not user relevant
DatID: Not user relevant
0xE722
Internal error - Please contact the hotline!
ZINFO1: Channel-Event
0: Channel offline
1: Bus error
2: Internal error
ZINFO2: Master system ID
DatID: Not user relevant
0xE723
Internal error - Please contact the hotline!
ZINFO1: Error code
1: Parameter error
2: Configuration error
ZINFO2: Master system ID
DatID: Not user relevant
0xE780
Internal error - Please contact the hotline!
0xE781
Address range exceeds process image limit
ZINFO1: Address
VIPA System 300S
+
System specific event IDs
HB140 | CPU-SC | 313-5BF23 | en | 19-01