Order no.
313-5BF23
Output voltage ranges
-10 V ... +10 V
0 V ... +10 V
Operational limit of voltage ranges
+/-0.2%
Basic error limit voltage ranges with SFU
+/-0.1%
Destruction limit against external applied voltage
max. 16V (30V / 10s)
Current outputs
ü
Max. in load resistance (current range)
500 Ω
Max. inductive load (current range)
100 µH
Typ. open circuit voltage current output
15 V
Output current ranges
-20 mA ... +20 mA
0 mA ... +20 mA
+4 mA ... +20 mA
Operational limit of current ranges
+/-0.3%
Radical error limit current ranges with SFU
+/-0.2%
Destruction limit against external applied voltage
max. 16V (30V / 10s)
Settling time for ohmic load
0.5 ms
Settling time for capacitive load
0.5 ms
Settling time for inductive load
0.5 ms
Resolution in bit
12
Conversion time
1 ms
Substitute value can be applied
no
Output data size
4 Byte
Technical data counters
Number of counters
3
Counter width
32 Bit
Maximum input frequency
30 kHz
Maximum count frequency
30 kHz
Mode incremental encoder
ü
Mode pulse / direction
ü
Mode pulse
ü
Mode frequency counter
ü
Mode period measurement
ü
Gate input available
ü
Latch input available
ü
Reset input available
-
Counter output available
ü
VIPA System 300S
+
Hardware description
Technical data
HB140 | CPU-SC | 313-5BF23 | en | 19-01
42