6.
Confirm with [Assign IP configuration].
ð
Direct after the assignment the Ethernet PG/OP channel may be reached online
by these address data. The value remains as long as it is reassigned, it is over-
written by a hardware configuration or an factory reset is executed.
1.
Open the Siemens hardware configurator und configure the Siemens CPU 313C
(6ES7 313-5BF03-0AB0 V2.6).
2.
Configure the modules at the standard bus.
3.
For the Ethernet PG/OP channel you have to configure a Siemens CP 343-1
(SIMATIC 300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX11 0XE0)
always below the really plugged modules.
4.
Open the property window via double-click on the CP 343-1EX11 and enter for the
CP at
‘Properties’
the IP address data, which you have assigned before.
5.
Assign the CP to a
‘Subnet’
. Without assignment the IP address data are not used!
6.
Transfer your project.
5.8 CPU parametrization
5.8.1 Parametrization via Siemens CPU
Since the CPU is to be configured as Siemens CPU 313C (6ES7 313-5BF03-0AB0 V2.6)
in the Siemens hardware configurator, the parameters of the CPU 313-5BF23 may be set
with "Object properties" of the CPU 313C during hardware configuration. Via a double-
click on the CPU 313C the parameter window of the CPU may be accessed. Using the
registers you get access to every parameter of the CPU.
Take IP address parame-
ters in project
Parameterization via Sie-
mens CPU 313C
VIPA System 300S
+
Deployment CPU 313-5BF23
CPU parametrization > Parametrization via Siemens CPU
HB140 | CPU-SC | 313-5BF23 | en | 19-01
55