Byte
Bit 7 ... Bit 0
Default
5
8h: Voltage 0...10V
9h: V/-10V
Measuring type:
0h: deactivated
1h: U Voltage
2h: I Current
3h: I Current
Measurement Analog Input Channel 2
n
Bit 3 ... 0: Measuring range
n
Bit 7 ... 4: Measuring type
19h
6
Measurement Analog Input Channel 3
n
Bit 3 ... 0: Measuring range
n
Bit 7 ... 4: Measuring type
19h
7
Measurement Analog Input Channel 4
n
Bit 3 ... 0: Measuring range
n
Bit 7 ... 4: Measuring type
Measurement range only channel 4:
0h: deactivated
2h: 600Ohm
6h: Pt100
Measurement type only channel 4:
0h: deactivated
6h: Resistor
15h: Resistance thermometer
62h
8...10
reserved
11
Analog Output Channel 0
n
Bit 3 ... 0: Output range
n
Bit 7 ... 4: Output type
Output range:
0h: deactivated
2h: Current 0...20mA
3h: Current 4...20mA
4h: C/-20mA
8h: Voltage 0...10V
9h: V/-10V
Output type:
0h: deactivated
1h: U Voltage
3h: I Current
19h
12
Analog Output Channel 1
n
Bit 3 ... 0: Output range
n
Bit 7 ... 4: Output type
19h
*) Here the VIPA CPU uses internally the value 1.25ms respectively 800Hz.
6.5 Digital part
The digital part consists of 24 input-, 16 output channels and 3 channels for technological
functions. Each of these digital input- respectively output channels shows its state via a
LED. By means of the parameterization you may assign interrupt properties to the inputs I
+0.0 to I+1.7.
313-5BF23
VIPA System 300S
+
Deployment I/O periphery
Digital part
HB140 | CPU-SC | 313-5BF23 | en | 19-01
101