Here it should apply:
n
if value1 = value2 activate output Q 124.0
n
if value1 > value2 activate output Q 124.1
n
if value1 < value2 activate output Q 124.2
n
You have administrator rights for your PC.
n
WinPLC7 is installed and activated as "Profi" version.
n
One SPEED7 CPU and one digital output module are installed and cabled.
n
The Ethernet PG/OP channel of the CPU is connected to your Ethernet network. Your
CPU may be connected to your PC with an Ethernet cable either directly or via hub/
switch.
n
WinPCap for station search via Ethernet is installed.
n
The power supply of the CPU and the I/O periphery are activated and the CPU is in
STOP state.
8.3.2 Project engineering
1.
Start WinPLC7 ("Profi" version)
2.
Create and open a new project with [Create a new solution].
1.
For the call of the hardware configurator it is necessary to set WinPLC7 from the
Simulator-Mode to the Offline-Mode. For this and the communication via Ethernet
set "Target: TCP/IP Direct".
2.
Double click to
‘Hardware stations’
and here at
‘Create new’
.
3.
Enter a station name. Please consider that the name does not contain any spaces.
4.
After the load animation choose in the register Select PLC-System the system
"VIPA SPEED7" and click to [Create]. A new station is created.
5.
Save the empty station with
[Strg]
+
[S]
.
6.
By double click or drag&drop the according VIPA CPU in the hardware catalog at
‘CPU SPEED7’
the CPU is inserted to your configuration.
7.
For output place a digital output module, assign the start address 124 and save the
hardware configuration.
Precondition
Hardware configuration
VIPA System 300S
+
WinPLC7
Example project engineering > Project engineering
HB140 | CPU-SC | 313-5BF23 | en | 19-01
171