A cable has to be terminated with its surge impedance. For this you switch on the termi-
nating resistor at the first and the last participant of a network or a segment. Please make
sure that the participants with the activated terminating resistors are always power sup-
plied. Otherwise it may cause interferences on the bus.
1
MPI programming cable
2
Activate the terminating resistor via switch
3
MPI network
1.
Connect your PC to the MPI jack of your CPU via a MPI programming cable.
2.
Load your project in the Siemens SIMATIC Manager.
3.
Choose in the menu
‘Options
è
Set PG/PC interface’
.
4.
Select in the according list the "PC Adapter (MPI)"; if appropriate you have to add it
first, then click on [Properties].
5.
Set in the register MPI the transfer parameters of your MPI net and type a valid
address
.
6.
Switch to the register
Local connection
.
7.
Set the COM port of the PC and the transfer rate 38400baud for the MPI program-
ming cable.
8.
Transfer your project via
‘PLC
è
Load to module’
via MPI to the CPU and save it
with
‘PLC
è
Copy RAM to ROM’
on a memory card if one is plugged.
5.9.2 Transfer via Ethernet
For transfer via Ethernet the CPU has the following interface:
n
X5: Ethernet PG/OP channel
So that you may access the Ethernet PG/OP channel you have to assign IP address
parameters by means of the "initialization".
Chap. 5.7 ‘Hardware configuration -
Ethernet PG/OP channel’ page 54
1.
For the transfer, connect, if not already done, the appropriate Ethernet port to your
Ethernet.
2.
Open your project with the Siemens SIMATIC Manager.
3.
Set via
‘Options
è
Set PG/PC Interface’
the access path to "TCP/IP
®
Network
card .... ".
Terminating resistor
Proceeding transfer via
MPI interface
Initialization
Transfer
VIPA System 300S
+
Deployment CPU 313-5BF23
Project transfer > Transfer via Ethernet
HB140 | CPU-SC | 313-5BF23 | en | 19-01
59