YASKAWA TOEPYAIUPW02A U1000 iQpump Drive Quick Start Procedure
U1000 iQpump Drive
Quick Start Procedure
Page 3
of 25
Identify the Model for Installation
1
STEP
Safety Symbols in
this Document
WARNING!
Read and understand
users manual before
using this equipment.
Failure to follow users
instructions may result
in serious injury or
death.
WARNING!
Hazardous Voltage.
Contact may cause
electric shock or burn.
Turn-off and lock-out
system and facility
power before servicing.
WARNING!
Stay Clear- Equipment
starts automatically.
Clear all personnel
from equipment, install
shields or guards, locate
and verify emergency
SHUT-OFF is functional.
Failure to comply may
result in serious injury to
personnel.
WARNING!
Improper Operation
Sequence. DO NOT
RUN THE MOTOR.
Failure to comply may
result in serious injury to
personnel.
WARNING!
Do not operate
equipment with covers
or guards removed.
Install or replace cover
and/or guards before
operation. Failure to
comply may result
in serious injury to
personnel.
This Quick Start Procedure serves as general guide to help install, configure and perform test run operation.
Refer to the U1000 iQpump Drive User Manual No. TOEPYAIUPW01 for complete instructions to configure this
product for each specific installation site.
Terminology
U1000 iQpump Drive is referred to as “drive” throughout this document.
1.1 Verify the correct model and ratings.
Follow this procedure for each drive and motor combination.
a. Locate the nameplate and your order information.
b.
Verify the Model Number matches the line item(s) on your order, to confirm receipt of the
correct model.
c. Locate the nameplate of motor that will be connected.
d.
Confirm the motor nameplate Amperage, Voltage, and Frequency (Hz) are within the Output
specifications shown on the drive nameplate.
1.2 Verify main power source is adequate by reviewing the Input
specifications shown on the drive nameplate.
PRG : 0000
IND.CONT.EQ.
7J48
CIMR-UW2A0028AUA
YASKAWA ELECTRIC CORPORATION
Assembled in U.S.A.
:
: AC3PH 200-240V 50/60Hz 25A
: AC3PH 0-240V 0-400Hz 28A
: 21 kg
: 6W3050-2-100
: J0073D207410100
: E131457
PASS
MODEL
C / C
: CIMR-UW2A0028AUA
INPUT
OUTPUT
MASS
O / N
S / N
FILE NO
IP00
REV : A
2-1 Kurosaki-shiroishi, Yahatanishi-Ku Kitakyushu 806-0004 Japan
Weight
Input Power
Rating
Output Power
Rating
Drive Model
Number
Serial
Number
UL File
Number
Drive Spec Number
Software
Version
Normal
Duty Amps
Enclosure Type