No.
Parameter Name
Setting Values
P6-21
Low Flow Detection Delay @ Start Cancel Time
Default: 5 s
Range: 0 to 6000 s
P6-22
Flow Meter Decimal Place Position
Default: 1
Range: 0 to 2
P6-26
Flow Limit Selection
Default: 0
Range: 0 to 2
P6-27
Flow Limit Level
Default: 0.0
Range: 0.0 to 6000.0
P6-28
Flow Limit Regulator Gain
Default: 0.00
Range: 0.00 to 25.00
P6-29
Flow Limit Regulator Integral Time
Default: 1.00 s
Range: 0.00 to 25.00 s
P6-30
Flow Limit Regulator Delay @ Start
Default: 10 s
Range: 0 to 6000 s
P6-35
Accumulator Delta Save Selection
Default: 0
Range: 0 to 2
P6-36
Delta Starting Accumulation Level - Millions
Default: 0
Range: 0 to 65535
P6-37
Delta Starting Accumulation Level - Thousands
Default: 0
Range: 0 to 999
P6-38
Delta Starting Accumulation Level - Ones
Default: 0
Range: 0 to 999
P6-39
Delta Starting Accumulation Level - Decimal
Default: 0.0000
Range: 0.0000 to 0.9999
U1-83
Flow Rate
Full scale: P6-01 Setting
U1-88
Total Volume Accumulated
Full scale: N/A
U1-89
Delta Volume Accumulated
Full scale: N/A
H2 Multi-Function Digital Output Settings
H2-
oo
Function
Description
A7
Flow Rate Limit
Closed: The Flow Rate is actively affecting the output speed.
4.6 U1000 iQpump Presets and Functions
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
131
4
Start-Up Programming & Operation