P3-50: Pump 2 Frequency Shutdown Level
Sets the level at which the first lag pump (2nd pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
level for the time set in P3-09, the pump will be de-staged.
No.
Parameter Name
Setting Range
Default
P3-50
Pump 2 Frequency Shutdown Level
0.0 to 400.0
40.0 Hz
n
P3-60: Pump 3 Frequency Shutdown Level
Sets the level at which the second lag pump (3rd pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
level for the time set in P3-09, the pump will be de-staged.
No.
Parameter Name
Setting Range
Default
P3-60
Pump 3 Frequency Shutdown Level
0.0 to 400.0
40.0 Hz
n
P3-70: Pump 4 Frequency Shutdown Level
Sets the level at which the third lag pump (4th pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
level for the time set in P3-09, the pump will be de-staged.
No.
Parameter Name
Setting Range
Default
P3-70
Pump 4 Frequency Shutdown Level
0.0 to 400.0
40.0 Hz
n
P3-80: Pump 5 Frequency Shutdown Level
Sets the level at which the third lag pump (5th pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
level for the time set in P3-09, the pump will be de-staged.
No.
Parameter Name
Setting Range
Default
P3-80
Pump 5 Frequency Shutdown Level
0.0 to 400.0
40.0 Hz
n
P3-90: Pump 6 Frequency Shutdown Level
Sets the level at which the third lag pump (6th pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
level for the time set in P3-09, the pump will be de-staged.
No.
Parameter Name
Setting Range
Default
P3-90
Pump 6 Frequency Shutdown Level
0.0 to 400.0
40.0 Hz
n
P4-01: Pre-Charge Level
Sets the level at which the drive will activate the pre-charge function. At start, if the PID is below the P4-01 setting, the drive
will run at the P4-02 frequency setting for the time set in P4-03. PID control is delayed until the pre-charge function stops.
The drive will exit the pre-charge function early if the feedback rises above the P4-01 setting or if a Low Water digital input
switch (H1-
oo
= 8F) deactivates. Pre-charge is useful to slowly fill or pressurize a system.
No.
Parameter Name
Setting Range
Default
P4-01
Pre-Charge Level
0.0 to 6000.0
<1> Units determined by P1–02 setting.
n
P4-02: Pre-Charge Frequency
Sets the frequency at which the pre-charge function will run.
No.
Parameter Name
Setting Range
Default
P4-02
Pre-Charge Frequency
0.0 to E1-04
0.0 Hz
n
P4-03: Pre-Charge Time
Sets the duration of time that the pre-charge function will run.