No.
Name
Setting Range
Default
S2-01
Sequence Timer 1 Start Time
12:00AM to 11:59PM
12:00AM
S2-06
Sequence Timer 2 Start Time
12:00AM to 11:59PM
12:00AM
S2-11
Sequence Timer 3 Start Time
12:00AM to 11:59PM
12:00AM
S2-16
Sequence Timer 4 Start Time
12:00AM to 11:59PM
12:00AM
<1> Default is 00:00 and range is 00:00 to 24:00 when o4-20 is set to 1 (24-hour).
n
S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection
Sets the action that occurs when sequence timers 1 to 4 are active.
No.
Name
Setting Range
Default
S2-04
Sequence Timer 1 Selection
0 to 3
0
S2-09
Sequence Timer 2 Selection
0 to 3
0
S2-14
Sequence Timer 3 Selection
0 to 3
0
S2-19
Sequence Timer 4 Selection
0 to 3
0
Setting 0: Digital Output Only
Setting 1: Run
Setting 2: Run - PI Disable
Setting 3: Allow Alternation
When Sequence Selection is set to Allow Alternation and that timer is enabled (S2-03, S2-08, S2-13, S2-18 > 0), the drive
will only allow 2 Motor alternation to occur during the time specified in the corresponding Sequence Timer. Alternation is
disabled when the timer deactivates.
4.7 Basic U1000 iQpump Setup and Application Preset Parameters
174
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual