5.5 Operator Programming Errors
u
Operator Programming Error Codes, Causes, and Possible Solutions
An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an
inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not
trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to
for the appropriate action. When
an oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is causing the oPE.
Table 5.6 oPE Codes, Causes, and Possible Solutions
HOA Keypad Display
Error Name
oPE01
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Cause
Possible Solutions
The drive model selection (o2-04) and the actual
capacity of the drive are not the same.
Correct the value set to o2-04.
HOA Keypad Display
Error Name
oPE02
Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.
Cause
Possible Solutions
Parameters were set outside the possible setting
range.
Set parameters to the proper values.
Note:
When multiple errors occur simultaneously, other errors are given precedence over oPE02.
HOA Keypad Display
Error Name
oPE03
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-08.
Cause
Possible Solutions
• The same function is assigned to two
multi-function inputs.
• Excludes “Not used” and “External Fault.”
• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.
The Up command was set but the Down command
was not, or vice versa (settings 10 vs. 11).
Properly set the functions that required for use in combination with other functions.
The Up 2 command was set but the Down 2
command was not, or vice versa (settings 75 vs.
76).
• Run/Stop command for a 2-wire sequence was
set (H1-
oo
= 42), but Forward/Reverse
command (H1-
oo
= 43) was not.
• “Drive Enable” is set to multi-function input S1
or S2 (H1-01 = 6A or H1-02 = 6A).
Properly set the functions that required for use in combination with other functions.
Two of the following functions are set
simultaneously:
• Up/Down Command (10 vs. 11)
• Up 2/Down 2 Command (75 vs. 76)
• Hold Accel/Decel Stop (A)
• Analog Frequency Reference Sample/Hold (1E)
• Check if contradictory settings have simultaneously been assigned to the multi-function input
terminals.
• Correct setting errors.
The Up/Down command (10, 11) and PID control
(b5-01) are enabled simultaneously.
Set b5-01 to 0 to disable control PID or disable the Up/Down command.
5.5 Operator Programming Errors
212
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual