B.8 H Parameters: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
u
H1: Multi-Function Digital Inputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H1-01
(0438)
Multi-Function Digital
Input Terminal S1
Function Selection
Term S1 Func Sel
Assigns a function to the multi-function digital inputs.
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: 40 (F)
Min.: 0
Max.: B0
H1-02
(0439)
Multi-Function Digital
Input Terminal S2
Function Selection
Term S2 Func Sel
Assigns a function to the multi-function digital inputs.
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: F (F)
Min.: 0
Max.: B0
H1-03
(0400)
Multi-Function Digital
Input Terminal S3
Function Selection
Term S3 Func Sel
Assigns a function to the multi-function digital inputs.
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: 26
Min.: 0
Max.: B0
H1-04
(0401)
Multi-Function Digital
Input Terminal S4
Function Selection
Term S4 Func Sel
Assigns a function to the multi-function digital inputs.
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: 14
Min.: 0
Max.: 9F
H1-05
(0402)
Multi-Function Digital
Input Terminal S5
Function Selection
Term S5 Func Sel
Assigns a function to the multi-function digital inputs.
for descriptions of setting values.
Note:
Set unused terminals to F.
Min.: 0
Max.: B0
H1-06
(0403)
Multi-Function Digital
Input Terminal S6
Function Selection
Term S6 Func Sel
Assigns a function to the multi-function digital inputs.
for descriptions of setting values.
Note:
Set unused terminals to F.
Min.: 0
Max.: B0
H1-07
(0404)
Multi-Function Digital
Input Terminal S7
Function Selection
Term S7 Func Sel
Assigns a function to the multi-function digital inputs.
for descriptions of setting values.
Note:
Set unused terminals to F.
Min.: 0
Max.: B0
H1-08
(0405)
Multi-Function Digital
Input Terminal S8
Function Selection
Term S8 Func Sel
Assigns a function to the multi-function digital inputs.
for descriptions of setting values.
Note:
Set unused terminals to F.
Default: F
Min.: 0
Max.: B0
H1-31
(09E1) Terminal S1 On-Delay
Time
Term S1 On-Delay
Sets the length of time that Terminal S1 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-32
(09E2) Terminal S2 On-Delay
Time
Term S2 On-Delay
Sets the length of time that Terminal S2 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-33
(09E3) Terminal S3 On-Delay
Time
Term S3 On-Delay
Sets the length of time that Terminal S3 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-34
(09E4) Terminal S4 On-Delay
Time
Term S4 On-Delay
Sets the length of time that Terminal S4 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-35
(09E5) Terminal S5 On-Delay
Time
Term S5 On-Delay
Sets the length of time that Terminal S5 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-36
(09E6) Terminal S6 On-Delay
Time
Term S6 On-Delay
Sets the length of time that Terminal S6 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-37
(09E7) Terminal S7 On-Delay
Time
Term S7 On-Delay
Sets the length of time that Terminal S7 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
H1-38
(09E8) Terminal S8 On-Delay
Time
Term S8 On-Delay
Sets the length of time that Terminal S8 must be closed before
the drive performs the programmed function.
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
–
B.8 H Parameters: Multi-Function Terminals
300
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual