No.
Name
Unit
–
Drive Model
–
4
o
0011
4
o
0014
4
o
0021
4
o
0027
o2-04
Drive Model Selection
Hex.
95
97
99
9A
E2-11
Motor Rated Output
kW (HP)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
L2-03
Momentary Power Loss Minimum Baseblock Time
s
0.3
0.3
0.3
0.3
L2-04
Momentary Power Loss Voltage Recovery Time
s
300
300
300
300
L2-21
Low Input Voltage Detection Level
V
300
300
300
300
L8-02
Overheat Alarm Level
°C
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
Table B.10 400 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
–
Drive Model
–
4
o
0034
4
o
0040
4
o
0052
4
o
0065
o2-04
Drive Model Selection
Hex.
9C
9D
9E
9F
E2-11
Motor Rated Output
kW (HP)
18.5 (25)
22 (30)
30 (40)
37 (50)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
126.26
115.74
103.58
92.54
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
26.5
32.9
38.6
52.3
E2-02
Motor Rated Slip
Hz
1.6
1.67
1.7
1.8
E2-03
Motor No-Load Current
A
7.6
7.8
9.2
10.9
E2-05
Motor Line-to-Line Resistance
Ω
0.55
0.403
0.316
0.269
E2-06
Motor Leakage Inductance
%
17.2
20.1
23.5
20.7
E2-10
Motor Iron Loss for Torque Compensation
W
440
508
586
750
L2-02
Momentary Power Loss Ride-Thru Time
s
1
1
1
1.1
L2-03
Momentary Power Loss Minimum Baseblock Time
s
0.6
0.6
0.6
0.6
L2-04
Momentary Power Loss Voltage Recovery Time
s
300
300
300
300
L2-21
Low Input Voltage Detection Level
V
300
300
300
300
L8-02
Overheat Alarm Level
°C
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
Table B.11 400 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
–
Drive Model
–
4
o
0077
4
o
0096
4
o
0124
4
o
0156
o2-04
Drive Model Selection
Hex.
A1
A2
A3
A4
E2-11
Motor Rated Output
kW (HP)
45 (60)
55 (75)
75 (100)
90 (125)
b3-04
V/f Gain during Speed Search
%
100
100
80
60
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.8
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
2.00
2.00
b8-04
Energy Saving Coefficient Value
–
76.32
71.56
67.2
46.2
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
65.6
79.7
95
130
E2-02
Motor Rated Slip
Hz
1.33
1.6
1.46
1.39
E2-03
Motor No-Load Current
A
19.1
22
24
36
B.19 Defaults by Drive Model