Programming 99
H3-09 Terminal A2 Function Selection
The A2 or A3 analog input can be programmed to perform many different functions. The setting of parameter H3-09 and
H3-05 determines which of the following functions the A2 or A3 analog input will respectively perform. The level of the A2
analog input, as a percentage of the maximum input, can be viewed by the U1-16 monitor.
Function: Adds to Terminal A1
Setting: 0
By setting analog input to 0 the level of the analog input will be summed with the level of the frequency reference analog input A1.
Function: Frequency Gain
Setting: 1
Setting analog input to 1 allows the analog input to act as a gain to the frequency reference.
Fig. 68 Frequency Reference Gain
Table 20 Analog Input Functions
Parameter
Setting
Function
Control Method (A1-02)
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
0
Adds to Terminal A1
(factory default, H3-09)
O
O
O
O
1
Frequency Reference Gain
O
O
O
O
2
Aux. Frequency Reference 1
(factory default, H3-05)
O
O
O
O
3
Aux. Frequency Reference 2
O
O
O
O
4
Output Voltage Bias
O
O
X
X
5
Accel / Decel Time Coefficient
O
O
O
O
6
DC Injection Braking Current
O
O
O
X
7
Overtorque / Undertorque Detection Level
O
O
O
O
8
Stall Prevention Level During Run
O
O
X
X
9
Frequency Reference Lower Limit
O
O
O
O
A
Jump Frequency 4
O
O
O
O
B
PID Feedback
O
O
O
O
C
PID Set Point
O
O
O
O
D
Frequency Reference Bias 2
O
O
O
O
E
Motor Temperature
O
O
O
O
10
FWD Torque Limit
X
X
O
O
11
REV Torque Limit
X
X
O
O
12
Regenerative Torque Limit
X
X
O
O
13
Torque Reference
X
X
X
O
14
Torque Compensation
X
X
X
O
15
FWD/ REV Torque Limit
X
X
O
O
1F
Not Used
O
O
O
O
1: Frequency Reference Gain
100%
-10V
10V
-100%
0V
20mA
4mA