Programming 138
o1-02 Power-On Monitor
When the Drive is powered up, three monitors are displayed on the digital operator. The first and largest monitor is the
“Power-On” monitor. The factory default “Power-On monitor” is frequency reference (U1-01). Below the frequency reference
monitor are the next two sequential monitors, Output Frequency (U1-02) and Output Current (U1-03). Pressing the
INCREASE key once scrolls the monitors to show the User Monitor as selected by o1-01. The factory default for o1-01 is the
Output Voltage monitor (U1-06).
The active monitor displayed when the Drive is powered on can be changed to either be U1-01 (frequency reference), U1-02
(Output Frequency), U1-03 (Output Current), or the User Monitor. Whichever monitor is selected as the Power-On top
monitor, the two monitors displayed below it are the next two sequential monitors. See example below.
For example, if the Drive needs to display the Elapsed Timer as the Power-On monitor, then o1-01 must be set to “13” and
o1-02 must be set to “4”. The next time Drive power is cycled, the digital operator displays U1-13 (Elapsed Time), U1-14
(Flash ID), and U1-15 (Term AI Level).
Setting
Description
1
Frequency Reference (
factory default
)
2
Output Frequency
3
Output Current
4
User Monitor (set by o1-01)
-DRIVE- Rdy
Frequency Ref
U1-
01
= 60.00Hz
- - - - - - - - - - - - - - - - - - - - - - - - - - - - -
U1-02= 60.00Hz
U1-03= 10.05A
Active Monitor
Next two
sequential
monitors
Active Monitor Title
Output Frequency
Output Current
-DRIVE- Rdy
Elapsed Time
U1-13= 2
H
- - - - - - - - - - - - - - - - - - - - - - - - - - - - -
U1-14= 03010
U1-16= 51.2%
Active Monitor
Active Monitor Title
Next two
sequential
monitors
Flash ID
Term AI Level
15