Front panel thickness
3 ... 12mm
Installation cutting (W x H)
547 x 367mm
Front panel (W x H x T)
562.4 x 382.4 x 6.7mm
Rear panel (W x H x D)
542 x 362 x 54.2mm
Installation depth
54.2mm
The degrees of protection are only guaranteed when the
following is observed:
–
The material thickness of the installation cut-out is 3 ...
12mm.
–
The deviation from the plane for the panel cut-out is
£
0.5mm.
–
Permissible surface roughness in the area of the seal:
£
120µm (friction coefficient 120)
21.5" - 67S-PNJ0-...
VIPA HMI PPC021 CE
Hardware description
Dimensions
HB160 | PPC | 67S-PNJ0 | GB | 15-30