3.17.4
Modifications
1.
Switch off the 24 V DC power supply for your System SLIO and disassemble the
corresponding System SLIO safety module.
2.
Switch all the switches of the F-address switch to 0 position.
3.
Mount the System SLIO safety module and switch on the DC 24V power supply for
your System SLIO, again.
4.
Wait 5s and then switch off the 24 V DC power supply again.
ð
The internal F-address memory of the System SLIOsafety module is cleared.
5.
Disassemble the System SLIO safety module again and set a new F-address at the
F-address switch, e.g. 3 (switch position 0000 0000 0011).
6.
Mount the System SLIO safety module and switch on the DC 24V power supply for
your System SLIO safety module, again.
7.
Open
YASKAWA SAFE CPU
with the project for the application example.
8.
Select
‘Project
è
FSoE bus Configurator’
and enter for the according System SLIO
safety modul at tab
‘FSoE master parameter’
at parameter
‘Slave ...: FSoE
Address’
the new F-address e.g. 3.
9.
Then proceed as follows by clicking on the corresponding buttons: [Validate Param-
eter], [Safe Project] and [Export Safe Container].
10.
Close the
FSoE Bus Configurator
.
11.
Compile and save the project using the corresponding buttons and transfer it to the
safety controller of the FSoE master.
ð
You now have an executable security program with a changed F-address.
1.
Open
YASKAWA SAFE CPU
with the project for the application example.
2.
Select
‘Project
è
FSoE bus Configurator’
and make the required parameter
changes in the
‘FSoE master parameter’
tab for the corresponding System SLIO
safety modul.
3.
Validate the parameter changes by activating the associated
‘Accept’
in the param-
eter table.
4.
Then proceed as follows by clicking on the corresponding buttons: [Safe Project]
and [Export Safe Container].
5.
Close the
FSoE Bus Configurator
.
6.
Compile and save the project using the corresponding buttons and transfer it to the
safety controller of the FSoE master.
ð
You now have an executable safety program with modified safety module
parameters.
Changing the F-address
Change parameters
VIPA System SLIO
Deployment
Sample application > Modifications
HB300 | SM-S | 02x-1SD10 | en | 20-02