Table 5.23 Sequence Timer Example 1 Parameter Settings
No.
Name
Setting
Comment
S2-01
Sequence Timer 1 Start Time
05:00
S2-02
Sequence Timer 1 Stop Time
15:00
S2-03
Sequence Timer 1 Day Selection
2
Mon to Fri
S2-04
Sequence Timer 1 Selection
1
Run
S2-05
Sequence Timer 1 Reference Source
0
Operator (d1-01)
S2-06
Sequence Timer 2 Start Time
19:00
S2-07
Sequence Timer 2 Stop Time
22:00
S2-08
Sequence Timer 2 Day Selection
2
Mon to Fri
S2-09
Sequence Timer 2 Selection
2
Run PI Disable
S2-10
Sequence Timer 2 Reference Source
1
Operator (d1-02)
S2-11
Sequence Timer 3 Start Time
06:00
S2-12
Sequence Timer 3 Stop Time
14:00
S2-13
Sequence Timer 3 Day Selection
3
Sat to Sun
S2-14
Sequence Timer 3 Selection
1
Run
S2-15
Sequence Timer 3 Reference Source
2
Operator (d1-03)
S2-16
Sequence Timer 4 Start Time
17:00
S2-17
Sequence Timer 4 Stop Time
21:00
S2-18
Sequence Timer 4 Day Selection
10
Sun
S2-19
Sequence Timer 4 Selection
0
Digital Output Only
S2-20
Sequence Timer 4 Reference Source
0
n/a
Mon
Tue
Wed
Thur
Fri
Sat
Sun
0:00
1:00
2:00
3:00
4:00
5:00
6:00
Sequence Timer 3
Run at d1-03
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00
Sequence Timer 4
18:00
19:00
Activate Sequence
20:00
Timer 4 digital output
21:00
22:00
23:00
Sequence Timer 1
Run at d1-01
Sequence Timer 2
Run at d1-02 with PI control disabled
Figure 5.51 Sequence Timer Example 1
n
Sequence Timer Example 2
Set the parameters as shown in
to accomplish the timer sequencing in
Table 5.24 Sequence Timer Example 2 Parameter Settings
No.
Name
Setting
Comment
S2-01
Sequence Timer 1 Start Time
00:00
S2-02
Sequence Timer 1 Stop Time
24:00
S2-03
Sequence Timer 1 Day Selection
2
Mon to Fri
S2-04
Sequence Timer 1 Selection
1
Run
S2-05
Sequence Timer 1 Reference Source
0
Operator (d1-01)
S2-06
Sequence Timer 2 Start Time
06:00
5.12 S: Special Parameters
190
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual