No.
Item
Page(s)
15
Set up overload protection circuits when running multiple motors from a single drive.
Thermal
relay
motor
Power supply
M1
oL1
oL2
M2
Drive
S3
(external fault)
N.O. input
oL1
oL2
SN
SC
SP
–
16
Verify that ground wiring for models 2E
oooo
/2W
oooo
/4E
oooo
/4W
oooo
is correct before turning on the
EMC filter switch.
17
Verify phase advancing capacitors, input noise filters, or GFCIs are NOT installed on the output side of the drive.
–
Control Circuit Wiring
18
Use twisted-pair line for all drive control circuit wiring.
19
Ground the shields of shielded wiring to the GND terminal.
20
For 3-Wire sequence, set parameters for multi-function contact input terminals S1 to S8, and wire control circuits.
–
21
Properly wire the option card.
22
Check for any other wiring mistakes. Only use a multimeter to check wiring.
–
23
Properly fasten drive control circuit terminal screws.
24
Pick up all wire clippings.
–
25
Ensure that no frayed wires on the terminal block are touching other terminals or connections.
–
26
Properly separate control circuit wiring and main circuit wiring.
–
27
Analog signal line wiring should not exceed 50 m.
–
28
Disconnect the internal EMC filter by moving the SW screw to the OFF position for floating, impedance grounded, or
asymmetrically grounded networks.