No.
Name
Display
Content
9
Function Key 2
(F2)
FWD/REV Pressing
F2
switches between forward and reverse.
DATA
Pressing
F2
scrolls to the next display.
→
Pressing
F2
scrolls the cursor to the right.
RESET
Pressing
F2
resets the existing drive fault error.
Monitor
Pressing
F2
switches Monitor mode.
DRV/BYP The multi-function relay selected Drive/Bypass contact will be toggled.
RUNBYP The multi-function relay selected to RUN Bypass will be toggled.
RLY
The multi-function relay selected to Relay operator control will be toggled.
<1> Displayed when in Frequency Reference Mode.
<2> Displayed when in Frequency Reference Mode and Monitor Mode.
u
AUTO LED and HAND LED Indications
Table i.25 AUTO LED and HAND LED Indications
AUTO LED
HAND LED
State
AUTO
Off
HAND
Off
OFF mode
AUTO
Off
HAND
On solid
HAND mode
AUTO
Off
HAND
Long blink (50% duty)
HAND mode when the Frequency Reference is 0 and/or decelerating in HAND mode.
AUTO
On solid
HAND
Off
Running in AUTO mode
AUTO
Long blink (50% duty)
HAND
Off
Running in AUTO mode when the Frequency Reference is 0 and/or decelerating in AUTO
mode.
AUTO
Short blink (15% duty)
HAND
Off
AUTO mode, Ready, No run command input.
AUTO
Double blink
HAND
Off
AUTO mode, stopped by a Fast- Stop from a Multi-Function Digital Input.
i.5 Start-Up Programming and Operation
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide
47