No.
Name
Description
H4-03
Multi-Function Analog
Output Terminal FM
Bias
Sets the signal level at terminal FM that is
equal to 0% of the selected monitor value.
H4-04
Multi-Function Analog
Output Terminal AM
Monitor Selection
Selects the data to be output through multi-
function analog output terminal AM.
Set the desired monitor parameter to the
digits available in U
o
-
oo
.
For example, enter “103” for U1-03.
H4-05
Multi-Function Analog
Output Terminal AM
Gain
Sets the signal level at terminal AM that is
equal to 100% of the selected monitor
value.
H4-06
Multi-Function Analog
Output Terminal AM
Bias
Sets the signal level at terminal AM that is
equal to 0% of the selected monitor value.
H4-07
Multi-Function Analog
Output Terminal FM
Signal Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20mA
H4-08
Multi-Function Analog
Output Terminal AM
Signal Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
H5-01 Drive Node Address
Selects drive station slave number (address)
for MEMOBUS/Modbus terminals R+, R-,
S+, S-.
Note:
Cycle power for the
setting to take effect.
H5-02 Communication Speed
Selection
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Note:
Cycle power for the
setting to take effect.
H5-03 Communication Parity
Selection
0: No parity
1: Even parity
2: Odd parity
Note:
Cycle power for the
setting to take effect.
H5-04
Stopping Method After
Communication Error
(CE)
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
4: Run at d1-04
H5-05 Communication Fault
Detection Selection
0: Disabled
1: Enabled. If communication is lost for
more than two seconds, a CE fault will
occur.
H5-06 Drive Transmit Wait
Time
Set the wait time between receiving and
sending data.
Note:
Cycle power for the
setting to take effect.
H5-07 RTS Control Selection
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when
sending.
Note:
Cycle power for the
setting to take effect.
H5-08 Communication
Protocol Selection
0: MEMOBUS/Modbus
1: N2 (Metasys)
2: P1 (APOGEE FLN)
3: BACnet
H5-09 CE Detection Time
Sets the time required to detect a
communications error.
Adjustment may be needed when
networking several drives.
No.
Name
Description
H5-10
Unit Selection for
MEMOBUS/Modbus
Register 0025H
0: 0.1 V units
1: 1 V units
H5-11
Communications
ENTER Function
Selection
0: Drive requires an Enter command
before accepting any changes to
parameter settings.
1: Parameter changes are activated
immediately without the Enter command.
H5-12 Run Command Method
Selection
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
L1-01 Motor Overload
Protection Selection
0: Disabled
1: General purpose motor (standard fan
cooled)
4: PM motor with variable torque
Default setting is determined by parameter
A1-02, Control Method Selection.
L1-02 Motor Overload
Protection Time
Sets the motor thermal overload protection
(oL1) time.
L1-03
Motor Overheat Alarm
Operation Selection
(PTC input)
Sets operation when the motor temperature
analog input
(H3-02 or H3-10 = E) exceeds the alarm
level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the
deceleration time in C1-09)
3: Alarm only (“oH3” will flash)
L1-04
Motor Overheat Fault
Operation Selection
(PTC input)
Sets stopping method when the motor
temperature analog input (H3-02, or H3-10
= E) exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the
deceleration time in C1-09)
L1-05
Motor Temperature
Input Filter Time (PTC
input)
Adjusts the filter for the motor temperature
analog input (H3-02, or H3-10 = E).
L1-08 oL1 Current Level
Sets the reference current for motor thermal
overload detection for the motor in
amperes.
L1-13
Continuous
Electrothermal
Operation Selection
0: Disabled
1: Enabled
2: Enable using Real Time Clock
L2-01 Momentary Power Loss
Operation Selection
0: Disabled.
Drive trips on Uv1 fault when power is lost.
1: Recover within the time set in L2-02.
Uv1 will be detected if power loss is longer
than L2-02.
2: Recover as long as CPU has power.
Uv1 is not detected.
L2-02 Momentary Power Loss
Ride-Thru Time
Sets the Power Loss Ride-Thru time.
Enabled only when L2-01 = 1.
L2-03
Momentary Power Loss
Minimum Baseblock
Time
Sets the minimum wait time for residual
motor voltage decay before the drive output
reenergizes after performing Power Loss
Ride-Thru.
Increasing the time set to L2-03 may help
if overcurrent or overvoltage occur during
Speed Search or during DC Injection
Braking.
Note:
Default setting is dependent upon
parameter o2-04, Drive Model Selection.
L4-05
Frequency Reference
Loss Detection
Selection
0: Stop. Drive stops when the frequency
reference is lost.
1: Run. Drive continues operation
according to the setting of L4-06.
L4-06 Frequency Reference at
Reference Loss
Sets the percentage of the frequency
reference that the drive should run with
when the frequency reference is lost.
i.8 Parameter Table
76
YASKAWA ELECTRIC TOEP C710636 11E Z1000U HVAC MATRIX Drive Quick Start Guide