background image

4.

 

Control parameter setting 

4.1.

 

Boot information 

full  screen  >>>  XMTN

N  shows  the  quantity  of  zones

>>>  V3.00

Software  version 

number

>>> normal condition 

4.2.

 

CHANNEL SELECT 

After long press        or        for one second, the current loop number starts flashing, and then 

short press        or        to switch the control loop. The N+1 channel is the temperature display 

of the environment (cold end of thermocouple). 

4.3.

 

Control parameter setting

 

    Long press        for 3 seconds to enter the setting state of control parameters.  At this time, 

the upper  row  displays  parameter  prompt  SV,  and  the  lower  row  displays  control parameters. 

At  this  point,  the  single  digit  flashes,  short  press        and  move  the  flshing  digits.  After 

selecting  the  number  of  digits  to  be  modified,  short  press          or          to  modify  the  control 

parameter. Continue to press        , and display each parameter prompt in the upper row. After 

finding  the  parameter  that  needs  to  be  modified,  continue  to  press        to  move  the  flshing 

digits. After selecting the number that needs to be modified, press        or        again to modify 

the control parameter. 

    Long press          for more than 1 second, the controller automatically returns to the normal 

control state (no button operation within 60 seconds, the controller automatically returns to the 

normal control state). 

4.4.

 

A list of control parameter Settings 

No. 

Parameter 

Name 

Symbol  Data Range  Unit 

Introductions 

Initial 

value 

Set value 

 

SVL

SVH 

 

The set target value of the zone of the controller 

100 

The lower 

limit alarm 1 

AL1 

-500

4000 

 

See 4.5, alarm output instructions for details 

50   

The lower 

limit alarm 2 

AL2 

-500

4000 

 

Same  as  AL1,  but  can  only  be  output  through 
communication 

50   

Upper limit 

alarm 1 

AH1 

-500

4000 

 

See 4.5, alarm output instructions for details 

50   

Upper limit 

alarm 2 

AH2 

-500

4000 

 

Same  as  AH1,  but  can  only  be  output  through 
communication 

50   

Alarm type 

SA 

00

66 

 

The single digit of XX is type 1 of alarm, while the 
ten digit is type 2 of alarm. X=0: no alarm; 1: upper 
limit deviation alarm; 2: lower limit deviation alarm; 
3:  alarm  outside  the  deviation  value  of  upper  and 
lower  limits;  4:  alarm  within  the  deviation  value  of 
upper  and  lower  limits;  5:  upper  absolute  value 
alarm;   

01 

Positive and 

negative 

action control 

and first 

power on 

alarm enable 

EA 

000

111 

 

The  hundred  digits  of  XXX  are  positive  and 
negative  control  options:  X=0:  reaction  control 
(heating  type);  1:  positive  action  control  (cooling 
type). The ten digit of XXX is first choice of alarm 
2, the single digit of XXX is first choice of alarm 1: 
X=0:  After  the  power  on  the  alarm  condition  does 
not  alarm,  then  all  alarm  if  the  alarm  condition  is 
met; 1: all alarm if the alarm condition is met. 

011 

Proportional 

band 

0

9999 

 

Regulation  of  proportional  action:  the  larger  the  P, 
the  smaller  the  proportional  action,  the  lower  the 
system  gain.  0:  change  to  on-off  control  mode.  At 
this  point,  the  integral  time  I  becomes  0.1  times  of 
the  upper  limit  of  the  insensitive  region  and  the 
differential  time  D  becomes  0.1  times  of  the  lower 
limit of the insensitive region.   

30   

Integral time 

0

9999 

Sec. 

Integral  action  time  constant:  the  larger  the  I,  the 
weaker the integral action, mainly used to eliminate 
the  static  difference.  0:  become  a  PD  control 
method,  the  integral inhibit  Ar  to  set  (RESET),  and 
the  Ar  is  set  to  zero,  the  unit  for 

,  is  used  to 

eliminate static error. When P=0, see the description 
of P.   

240 

10 

Differential 

Time 

0

9999 

Sec. 

Differential  action  time  constant:  the  larger  the  D, 
the  stronger  the  differential  action,  which  is  mainly 
used to restrain the overshoot of measured values. 
When P=0, see the description of P.   

60   

11 

Restrained 

Integration 

Ar 

0

100 

Restrained  Integration  ratio:  the  larger  the  Ar,  the 
larger  the  overthrust,  and  the  smaller  the  Ar,  the 
possible static difference. 
When  the  integral  time  I  is  equal  to  0,  see  the 
description of the integral time I 

100 

12 

Control cycle 

1

100 

Sec. 

Output of thyristor or solid-state relay: 2~3 seconds; 
Relay output: 20~30 seconds 

3   

13 

Sensor error 

correction 

Pb 

-500

4000 

 

Used to correct measurement error caused by sensor 
and thermocouple compensation wire 

0.0 

14 

Auto tuning 

At 

n

O or YES 

 

YES:  start  self-tuning  and  restore  nO  after 
self-tuning.  If  the  self-tuning  rule  is  not  completed 
within 4 hours, the original P, I and D values are still 
used for control. 

n

15 

Auto tuning 

Limit 

AtU 

0

100 

In  order to  overcome the  overshoot phenomenon  of 
the  Auto tuning time,  the  Auto tuning control  point 
can be lowered to SV x ATU. 

100 

16 

Graduation 

S

n

 

0

18 

 

See 1.2 list of commonly used input types and range 
for details. 

3-K 

17 

Decimal 

point 

dP 

0

 

0

the resolution of the measured values PV 1 

 

1

the resolution of the measured values PV 0.1 

 

18 

Filter 

coefficients 

FILt 

0

250 

 

The smaller this value, the faster the measured value 
responds,  but  there  may  be  fluctuations;  The  larger 
this  value,  the  slower  the  measured  value  response 
and the more stable the display. 

125 

19 

Screen 

blanking 

dt 

0

250 

 

Used  to  suppress  the  change  sensitivity  of  the 
display  value,  and  the  range  of  inhibition  is  0.1 
times of the display inhibition dt. 

15 

20 

Alarm1 

differential 

gap 

FH1 

-500

4000 

 

The differential gap is 0.1 times of FH1 

21 

Upper limit 

 

-500

4000 

 

The highest measured value is SVH 

300 

Reviews: