background image

Yingli Solar G/G Modules, Installation and User Manual 

page 3

Artificially concentrated light must not be directed on the front and rear surfaces 
of PV modules.

Design Recommendations

Yingli Solar recommends that PV modules shall be mounted at a minimum tilt 
angle of 10 degrees to allow for proper self-cleaning from normal rain showers.

PV modules are recommended to be installed at an optimized tilt angle to 
maximize the energy output. It is roughly equal to the latitude of the project 
site as a rule of thumb, facing the equator. But always to design based on local 
situations to find out the optimum one.  

Partial or complete shading of a PV module or modules can significantly reduce 
system performance. Yingli Solar recommends minimizing the amount of shade 
throughout the year to increase the amount of energy produced by the PV 
modules.  

Lightning protection is recommended for PV systems that are to be installed in 
locations with high probability of lightning strikes. 

High system voltages could be induced in the event of an indirect lightning 
strike, which could cause damage to PV system components. The open area 
of wire loops should be minimized (see Figure 5), in order to reduce the risk of 
lightning induced voltage surges.  

Figure 5: Wire loop design recommendation

Climate Conditions

PV modules may be installed in the following conditions for more than 30 years. 
In addition to the required IEC certification, PV modules have also been tested to 
verify resistance to ammonia fumes that may be present around barns sheltering 
cattle, as well as suitability for installation in humid (coastal) areas and areas of 
high sand storms.

Table 1: Environment of installation

E L E C T R I C A L   I N S TA L L AT I O N

Electrical Configuration

Under normal conditions, a PV module is likely to experience conditions that 
produce more current and/or voltage than reported at Standard Test Conditions 
(Irradiance: 1000 W/m

2

, 25°C cell temperature and AM 1.5). The short-circuit 

current (I

SC

) should be multiplied by a factor of 1.25 based on the highest 

ambient temperature recorded, and the open-circuit voltage (V

OC

) should be 

multiplied by a factor of up to 1.25 based on the lowest ambient temperature 
recorded for the installation location when determining component voltage 
ratings, conductor current ratings, fuse sizes, and size of controls connected to 

the PV output.  

This maximum voltage should not be exceeded at any time and, as the voltage of 
the module increases, above datasheet values, at operating temperatures below 
25°C, then these need to be taken into account when designing a PV system.

Voltages are additive when PV modules are connected directly in series, and 
module currents are additive when PV modules are connected directly in parallel 
(see Figure 6). PV modules with different electrical characteristics must not be 
connected directly in series. The use of unsuitable third-party electronic devices 
connected to PV modules may lead to mismatching, and must be installed 
according to the manufacturer’s specified instructions. 

Figure 6: Electrical diagrams of series and parallel wiring

The maximum voltage of the system must be less than the maximum certified 
voltage, 1500V typically, and the maximum input voltage of the inverter and 
of the other electrical devices installed in the system. To ensure that this is the 
case, the open circuit voltage of the array string needs to be calculated at the 
lowest expected ambient temperature for the location. This can be done by 
using the following formula.

Max System voltage 

 N * Voc * [1 + 

β

Voc

 * (Tmin-25)]

When the modules connect in parallel, the output current will be equal to the 
sum of each branch current. It is suggested that every series module string 
should be fused prior to be connected with other strings. Please refer to the 
applicable regional and local codes for additional fuse requirements. 

An appropriately rated overcurrent protection device must be used when the 
reverse current could exceed the value of the maximum fuse rating of the 
module. An overcurrent protection device is required for each series string if 
more than two series strings are connected in parallel. 

Cables and Wiring

Yingli Solar PV modules are provided with two (2) stranded, sunlight resistant 
output cables that are terminated with PV connectors ready for most installations. 
The positive (+) terminal has a female connector while the negative (-) terminal 
has a male connector. The module wiring is intended for series connections [i.e. 
female (+) to male (-) interconnections, as shown in Figure 7], but can also be 
used to connect suitable third-party electrical devices that may have alternative 
wiring configurations so long as the manufacturer’s   instructions are followed.  

Use field wiring with suitable cross-sectional areas that are approved for use at 
the maximum short-circuit current of the PV module. Yingli Solar recommends 
to use only sunlight resistant waterproof cables qualified for direct current (DC) 
wiring in PV systems. The minimum wire size should be 4 mm

2

.

Series Wiring (Voltage Additive)

Parallel Wiring (Current Additive)

Operating temperature

-40°C to +85°C

Storage temperature

-20°C to +50°C

Humidity

< 85%RH

Altitude

 2000m

Notes:

The modules have been evaluated by TUV according to IEC61215 for a maximum positive design loading 
of 3600 Pa, and negative design loading 1600 Pa, with 1.5 times safety factor.

The mechanical load bearing is dependent upon the mounting methods used and failure to follow the 
instructions in this manual may result in different capabilities to withstand snow and wind loads.

The system installer must ensure that the installation methods used meet these requirements and any 
local codes and regulations.

Where

N

Number of modules in series

Voc

Open circuit voltage of each module (refer to product label or datasheet)

β

Voc

Thermal coefficient of open circuit voltage for the module (refer to datasheet)

Tmin

The lowest ambient temperature

Summary of Contents for YGE G/G 60CL/F Series

Page 1: ...trol Failure to comply with the requirements listed in this manual will invalidate the Limited Warranty for PV modules as provided by Yingli Solar at the time of sale to the direct customer Additional...

Page 2: ...e short side of the box including the corresponding part of the upper lid and the bottom lid see Figure 4 Pay attention to not damage the modules during the cutting process Thirdly cut the two inner s...

Page 3: ...party electronic devices connected to PV modules may lead to mismatching and must be installed according to the manufacturer s specified instructions Figure 6 Electrical diagrams of series and parall...

Page 4: ...or optimal performance Yingli Solar recommends that the negative pole of the PV array be connected to ground Equipment Grounding The frame of the PV module as well as any exposed non current carrying...

Page 5: ...in the mechanical mounting instructions of this installation manual The installation shall follow the instructions below If the installation method is different from this manual please contact Yingli...

Page 6: ...taller or other qualified person The purpose of the PV system inspection is to ensure that all system components are functioning properly At a minimum this inspection should confirm the following All...

Page 7: ...e glass surface to enhance power output and reduce dirt and dust buildup In order to avoid module damage do not clean PV modules with a power washer or pressure washer Do not use steam or corrosive ch...

Page 8: ...8 9 18 1500 15 YL270PG2530L F 1 270 30 7 8 80 37 9 9 27 1500 15 YL275PG2530L F 1 275 31 0 8 90 37 9 9 35 1500 15 YL280PG2530L F 1 280 31 2 8 98 38 0 9 43 1500 15 YL285PG2530L F 1 285 31 4 9 08 38 1 9...

Page 9: ...coefficient C 0 05 0 32 0 42 YLM G G 72CL F YL330DG2536L F 2 330 37 1 8 90 45 2 9 46 1500 15 YL335DG2536L F 2 335 37 4 8 96 45 4 9 51 1500 15 YL340DG2536L F 2 340 37 7 9 02 45 6 9 56 1500 15 YL345DG25...

Page 10: ...n and User Manual page 10 CLAMP INSTALLATION DRAWINGS OF PV MODULES UNITS mm YGE G G 60CL YGE G G 72CL YLM G G 60CL YLM G G 72CL 992 1975 360 635 635 350 200 992 1975 360 635 635 350 200 360 953 345 9...

Page 11: ...3 8 Grounding holes 8 6 1981 365 633 633 350 100 998 1981 32 1981 998 Drainage holes 8 3 8 Grounding holes 8 6 365 633 633 350 100 998 1664 32 1664 998 365 949 350 Drainage holes 8 3 8 100 Grounding h...

Reviews: