Fitting pipe between manifolds
Pipe size (between two manifolds at indoor unit side) is based on the total capacity of upstream indoor unit(s).
Fig. 28
Total capacity of downstream indoor
unit(s) C(Btu/h)
Dimension of the pipe of indoor branch
Gas Pipe mm(in.)
Liquid Pipe mm(in.)
C≤17100
Φ12.7(1/2)
Φ12.7(1/2)
17100
<
C≤48500
Φ15.9(5/8)
Φ15.9(5/8)
48500
<
C≤72000
Φ19.05(3/4)
Φ19.05(3/4)
72000
<
C≤96000
Φ22.2(7/8)
Φ22.2(7/8)
96000
<
C≤144000
Φ28.6(1-1/8)
Φ28.6(1-1/8)
144000
<
C≤216000
Φ28.6(1-1/8)
Φ28.6(1-1/8)
216000
<
C≤240000
Φ34.9(1-3/8)
Φ34.9(1-3/8)
240000
<
C≤336000
Φ34.9(1-3/8)
Φ34.9(1-3/8)
336000
<
C
Φ41.3(1-5/8)
Φ41.3(1-5/8)