Power and Wiring
Connecting the cables
Indoor Unit
Connect the power cord to the indoor unit by attaching the wires to
the terminals on the control board individually, in accordance with the
outdoor unit connection.
Note: For some models, it is necessary to remove the cabinet to
connect to the indoor unit terminal
Outdoor Unit
1. Remove the Cable Cross Board from the unit by loosening
the screw. Connect the wires to the terminals on the control
board individually.
2. Secure the power cord to the control board with the cable
clamp.
3. Reinstall the Cable Cross Board to its original position.
4. Use a recommended HVAC circuit breaker between the
power source and the unit. A quick disconnect, installed near
the outdoor unit, that can disconnect all power supply lines must be fitted.
Always use a dedicated power circuit specifically for the air conditioner. For wiring requirements, refer to the
circuit diagram found inside the unit access door.
Confirm cable gauge as specified in the power supply specification.
Before running the unit, check the wires to ensure that they are all tightly attached.
Be sure to install ground fault circuit breaker in wet or moist areas.
Cable Specifications
Capacity (Btu/h)
Wire Sizes to ODU
Wire Sizes from ODU to IDU
Type
Normal cross-
sectional areas
Type
Normal cross-
sectional areas
9k-12k (208/230v)
SJTW
3x14 AWG
SJTW
4x18 AWG
18k-24k (208/230v)
SJTW
3x12 AWG
SJTW
4x16 AWG
24k-36 (208/230v)
SJTW
3x10 AWG
SJTW
4x16 AWG
9k (110v)
SJTW
3x12 AWG
SJTW
4x18 AWG
12k (110v)
SJTW
3x12 AWG
SJTW
4x18 AWG
ATTENTION:
Plug must be accessible after the installation of the appliance in the event that there is a need to
disconnect it. If not possible, connect the appliance to a double-pole circuit breaker with contact
separation of at least 3mm
2
placed in a position that is accessible after the installation.