IM 01C25B01-01E
2-4
2. HANDLING CAUTIONS
Note 2. Entity Parameters
• Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax = 30 V
Ci = 6 nF
Imax = 200 mA
Li = 0
µ
H
Pmax = 1 W
* Associated Apparatus Parameters
(FM approved barriers)
Voc
≤
30 V
Ca > 6 nF
Isc
≤
200 mA
La > 0
µ
H
Pmax
≤
1W
• Intrinsically Safe Apparatus Parameters
[Groups C, D, E, F and G]
Vmax = 30 V
Ci = 6 nF
Imax = 225 mA
Li = 0
µ
H
Pmax = 1 W
* Associated Apparatus Parameters
(FM approved barriers)
Voc
≤
30 V
Ca > 6 nF
Isc
≤
225 mA
La > 0
µ
H
Pmax
≤
1 W
• Entity Installation Requirements
Vmax
≥
Voc or Uo or Vt, Imax
≥
Isc or Io or It,
Pmax (or Po)
≤
Pi, Ca or Co
≥
Ci + Ccable,
La or Lo
≥
Li + Lcable
Note 3. Installation
• Barrier must be installed in an enclosure that meets
the requirements of ANSI/ISA S82.01.
• Control equipment connected to barrier must not use
or generate more than 250 V rms or V dc.
• Installation should be in accordance with ANSI/ISA
RP12.6 “Installation of Intrinsically Safe Systems for
Hazardous (Classified) Locations” and the National
Electric Code (ANSI/NFPA 70).
• The configuration of associated apparatus must be
FMRC Approved.
• Dust-tight conduit seal must be used when installed
in a Class II, III, Group E, F and G environments.
• Associated apparatus manufacturer’s installation
drawing must be followed when installing this
apparatus.
• The maximum power delivered from the barrier
must not exceed 1 W.
• Note a warning label worded “SUBSTITUTION OF
COMPONENTS MAY IMPAIR INTRINSIC
SAFETY,” and “INSTALL IN ACCORDANCE
WITH DOC. No. IFM022-A12”
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Factory Mutual Intrinsically safe and
Nonincendive Approval.
F0203-1.EPS
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Class 1, Zone 0 in
Hazardous (Classified)
Locations AEx ia IIC
EJX Series Pressure
Transmitters
Safety Barrier
Supply
Hazardous Location
Nonhazardous Location
General
Purpose
Equipment
+
–
+
–
+
–
+
–
[Intrinsically Safe]
F0203-2.EPS
EJX Series Pressure
Transmitters
Supply
Hazardous Location
Nonhazardous Location
+
–
+
–
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class III, Division 1.
Class 1, Zone 2, Group IIC,
in Hazardous (Classified)
Locations
Not Use
Safety Barrier
[Nonincendive]
General
Purpose
Equipment
b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model EJX Series differential, gauge,
and absolute pressure transmitters with
optional code /FF1 are applicable for
use in hazardous locations.
• Applicable Standard: FM3600, FM3615, FM3810,
ANSI/NEMA 250
• Explosionproof for Class I, Division 1, Groups B,
C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Enclosure rating: NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60
°
C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NFPA70 and Local Electrical Codes.