<9. Maintenance>
9-11
IM 01C27C01-01EN
Integral
indicator
Factory
NAMUR
category
Bit
Diagnostic
Status
Diagnostic Status Detail
Cause
Release/
recovery
conditions
(except
restart)
Action
AL.53
P. ADJ
C
Bit 25
Installation,
calibration
problem
DP_TRIM_SPAN_OUTSIDE Pressure span
adjustment
variable outside
of range
Recovers
when span
adjustment
variable/point
returns within
the range.
Check
the span
adjustment
variable for
the Pressure.
AL.53
P. ADJ
DP_TRIM_ZERO_OUTSIDE Pressure zero
adjustment
variable outside
of range
Recovers
when zero
adjustment
variable/point
returns within
the range.
Check
the zero
adjustment
variable for
the Pressure.
AL. 55
SP. ADJ
C
Bit 25
Installation,
calibration
problem
SP_TRIM_SPAN_OUTSIDE Static pressure
span adjustment
variable outside
of range
Recovers
when span
adjustment
variable /point
returns within
the range.
Check
the static
pressure
span
adjustment
variable.
AL. 55
SP. ADJ
SP_TRIM_ZERO_OUTSIDE Static pressure
zero adjustment
variable outside
of range
Recovers
when zero
adjustment
variable/point
returns within
the range.
Check
the static
pressure zero
adjustment
variable.
AL. 79
OV. DISP
LCD_OUTSIDE_LIMIT
LCD display
outside of
specified range
Recovers when
display value
returns within
the range.
Check the
display
setting.
AL. 30
RANGE
O
Bit 22
Environmental
conditions out
of device
specification
DP_OUTSIDE_RANGE
Input pressure
setting outside
of range
Recovers when
setting returns
within the
range.
Check the
input pressure
setting.
AL. 31
SP. RNG
SP_OUTSIDE_RANGE
Static pressure
setting outside
of range
Recovers when
setting returns
within the
range.
Check
the static
pressure
setting.
AL. 70
LOWBAT
M
Bit 20
Power is critical
low:
maintenance
need short -
term
CRITICAL_LOWBAT
Battery voltage
is the lowest.
None
Replace the
batteries.
AL. 70
LOWBAT
Bit 19
Power is
low:
maintenance
need mid - term
WL_LOWBAT_ALM
Low remaining
battery voltage
None
Replace the
batteries.
AL. 60
AI OOS
C
Bit 24 O/S
AI1_OUT_OF_SERVICE
AI1 block is O/S
mode.
Returns when
the mode target
of AI1 block is
other than O/S.
Set the mode
target to
AUTO.
AL. 61
AI OOS
AI2_OUT_OF_SERVICE
AI2 block is O/S
mode.
Returns when
the mode target
of AI2 block is
other than O/S.
Set the mode
target to
AUTO.
AL. 62
AI OOS
AI3_OUT_OF_SERVICE
AI3 block is O/S
mode.
Returns when
the mode target
of AI3 block is
other than O/S.
Set the mode
target to
AUTO.