background image

IM 01C22T01-01E

2-5

2.  HART COMMUNICATOR OPERATION

2.3 Parameters

2.3.1 Parameter Usage and Selection

Before describing the procedure for setting parameters,
we present the following table showing how the
prameters are used and in what case.

NOTE

Do not turn off the transmitter as soon as HART
Communicator settings (sending) have been
made. If the transmitter is turned of less than 30
seconds after parameters have been set, the set
data will not be stored and the terminal returns
to previous settings.

Table 2.3.1 Parameter Usage and Selection

Memory

Transmitter

Display

HART output

Monitoring

Maintenance

Adjustment

T0201.EPS

Item

HART Communicator

Description

Page

Tag

Descriptor

Message

Date

Unit

LRV/URV

Apply values

Xfer fnctn

Damp

Low cut

Cut mode

Bi-dire mode

H

2

O Unit select

Snsr temp unit

Static pres unit

Display fnctn

Display mode

Engr disp range

Burst option

Burst mode

Poll addr

Auto poll

Pres

% rnge

A01 out

Snsr temp

Static pres

Engr display

Loop test

Self test

Status

A01 Alarm typ

Ext SW mode

Write protect

Enable write

New password

Zero trim

Lower/Upper sensor trim

D/A trim, Scaled D/A trim

Tag number, Up to 8 characters

Up to 16 characters

Up to 32 characters

xx/yy/zz

Set the calibration range by the keypad

Range for 4 to 20 mA DC signal is set with actual input applied.

Linear or Zero

Used to measure bi-directional flows.

at 4

°

C (39.2

°

F)/at 20

°

C (68

°

F)

Sets a unit for temperature displayed on the model 275.

Sets a unit for static pressure displayed on the model 275.

Engr unit/Engr disp LRV/Engr disp URV/Engr disp point.

Selection of the data to be sent continuously (Pres/% rnge/A01 out).

ON/OFF switching of burst mode.

Setting the polling address (1 to 15).

ON/OFF switching of multi-drop mode.

Pressure variable

% output variable

4 to 20 mA output variable

Sensor temperature

Static pressure

Displays output as on an LCD. settable in the engr disp range.

Display of the result of self-test, calibration of transmitter.

Display the status of 4 to 20 mA DC output when a failure

Display/set the external volume protect/permit for LRV (URV) setting.

Setting a new password.

Set the current input value to 0 kPa.

Adjust only measured pressure variable.

Adjust the output value at the points of 4 mA and 20 mA.

Engineering unit

Range

Output mode

Damping time constant

Output signal low cut 
mode

Bi-direction flow 
measurement mode

H

2

O unit selection

Unit for displayed 
temperature

Unit for displayed static 
pressure

Integral indicator display 
mode

Integral indicator scale

Burst mode

Multi-drop mode

Test output

Self-diagnostics

Output when CPU error 
has occurred

External volume 
protect/permit

Software Write Protect

Zeroing

Sensor trim

Analog output trim

inH

2

O, inHG, ftH

2

O, mmH

2

O, mmHG, psi, bar, mbar, g/cm

2

, kg/cm

2

, Pa, kPa, MPa, torr, atm

Sets mode for output signal to “linear mode” (proportional to input differential pressure) 
or to “Square root mode” (proportional to flow).

Adjust the output response speed for 4 to 20 mA DC. 0.2, 0.5, 1, 1.5, 2, 4, 6, 8, 16, 32 
(sec)

Used mainly to stabilize output near 0 if output signal is the square root mode. Two 
mode are available: forcing output to 0% for input below a specific value, or changing to 
proportional output for input below a specific value.

Sets mode for integral indicator to “linear mode” (proportional to input differential 
pressure) or to “Square root mode” (proportional to flow).

Set the following 5 types of integral indicator scale ranges and unit: “% scale indicator”, 
“use set scale indicator”, “alternate indication of user set scale and % scale”, “input 
pressure display” and “alternate indication of input pressure and % scale.

Used for loop checks. Output can be set freely from –5% to 110% in 1% step.

Check using the self-test command. If an error is detected, the corresponding message 
is displayed.

Displays the permit/protect status of setting changes depending on communications.

Write protect status is released for 10 minutes when the password is entered.

P.2-7

P.2-8

P.2-9

P.2-10

P.2-19

P.2-12

P.2-10

P.2-10

P.2-16

P.2-11

P.2-12

P.2-13

P.2-14

P.2-19

P.1-2

P.2-17

Summary of Contents for Dpharp vigilantplant EJA Series

Page 1: ...User s Manual Yokogawa Electric Corporation Model EJA Series HART Protocol IM 01C22T01 01E IM 01C22T01 01E 7th Edition...

Page 2: ...ion 2 5 2 3 2 Menu Tree 2 6 2 3 3 Setting Parameters 2 7 1 Tag No 2 7 2 Unit 2 7 3 Range Change 2 7 4 Output Mode Linear Sq root 2 8 5 Damping Time Constants 2 9 6 Output Signal Low Cut Mode Setup 2 9...

Page 3: ...110 EJA120 IM 01C22B01 01E EJA210 EJA220 IM 01C22C01 01E EJA310 EJA430 IM 01C22D01 01E EJA118W EJA118N EJA118Y IM 01C22H01 01E EJA438W EJA438N IM 01C22J01 01E EJA115 IM 01C22K01 01E T01 EPS Manual No...

Page 4: ...adjustment will return the adjustment back to the previous settings Using the HART Communicator Zero point can be adjusted by simple key operation of the HART Communicator Select parameter Zero Trim a...

Page 5: ...smitter output 1383 mmH2O DPharp F0103 EPS 1 1 Device setup 2 Diag Service 3 Calibration 3 Sensor trim 2 Lower Sensor Trim EJA Apply low pressure ABORT OK F0104 EPS Check the tank level at present and...

Page 6: ...e setting push button The integral indicator then displays LSET 3 Apply a pressure of 0 kPa atmospheric pressure to the high pressure side of the transmitter Note 1 4 Turn the external zero adjustment...

Page 7: ...ging LRV automatically changes URV to the following value URV previous URV new LRV previous LRV 3 If the range setting push button and external zero adjustment screw are not touched during a range cha...

Page 8: ...from any terminal strip as well DPharp HART communicator Relaying terminals Distributor Control room Terminal board F0201 EPS HART communicator Figure 2 1 1 Interconnection Diagram 2 1 2 Communicatio...

Page 9: ...s the position where a number or character is to be entered Pressing calls up the display corresponding to the item pointed with the highlighting cursor Pressing returns to the previous display See 2...

Page 10: ...re establish communication EXIT leave the current menu YES answer to yes no question ALL include current Hot Key item on Hot Key Menu for all devices F2 ON OFF activates or deactivates a binary variab...

Page 11: ...is held in memory unless power is turned off every data can be sent to the transmitter at once Operation Entering data on the Tag setting display 1 Device setup 3 Basic setup 1 Tag F0206 EPS EJA YOKO...

Page 12: ...f self test calibration of transmitter Display the status of 4 to 20 mA DC output when a failure Display set the external volume protect permit for LRV URV setting Setting a new password Set the curre...

Page 13: ...m Point 1 Sensor Temperature 2 Sensor Temperature Unit 1 Static Pressure 2 Static Pressure Unit 1 PROCESS VARIABLES 2 RERANGE 3 Unit 4 Transfer Function 5 Damp 6 Low Cut 7 Cut Mode 8 Bi dir Mode 9 H2O...

Page 14: ...R 3 Select the desired engineering unit and press ENTER F4 HELP 3 ENTER Example To change the unit from mmH2O to inH2O F02111 EPS EJA keypad input 1 LRV 0 00 mmH2O 2 URV 3000 00 mmH2O 3 Unit inH2O 4 L...

Page 15: ...ABORT OK 3 Apply the pressure of 500mmH2O After obtaining a stable pressure press OK F4 ENTER OK OK 1 Device setup 3 Basic setup 3 Re range 2 Apply values Example To change the range from 0 to 2500 m...

Page 16: ...circuit The damping constant of the capsule assembly shall be added to obtain the overall damping constant of the transmitter Table 2 0 2 Sec 0 5 Sec 1 0 Sec 2 0 Sec 4 0 Sec 8 0 Sec 16 0 Sec 32 0 Sec...

Page 17: ...display Low Cut 4 mA 100 display Output mode SQUARE ROOT LRV HRV 8 Integral Indicator Display Mode F0220 EPS ENTER EJA Display fnctn Linear Linear Square Root HELP SEND ESC ENTER Select Square Root a...

Page 18: ...ing units to be displayed on the HART communicator When the instrument is shipped this is set as specified in the order Follow the procedure below to change this setting Since these units are not disp...

Page 19: ...nit from mmH2O to kPa inH2O inHg ftH2O mmH2O mmHg psi bar mbar g cm2 kg cm2 Pa kPa torr atm 12 Test Output This feature can be used to output a fixed current from 3 2 mA 5 to 21 6 mA 110 for loop chec...

Page 20: ...or zero shifts caused by static pressure See section 1 1 1 1 F02281 EPS Select the Lower Sensor trim EJA Sensor trim 1 Zero trim 2 Pres 3 Lower sensor trim 4 Upper sensor trim 5 Sensor trim points HE...

Page 21: ...000 HELP ESC 5 Enter the read value 4 115 of the ammeter and press ENTER F4 The output of the transmitter changes DEL ENTER ENTER 4 1 1 5 Example 1 For the adjustment using an ammeter 1 A is measurabl...

Page 22: ...Connect reference meter DEL SET ABORT OK 7 Connect the voltmeter and press OK F4 EJA Setting fld dev output to 4mA HELP DEL ABORT OK 8 Press OK F4 The output signal of 0 is output OK OK ENTER F0233 EP...

Page 23: ...lay and set to OFF 16 Multidrop Mode Multidropping transmitters refers to the connection of several transmitters to a single communications transmission line Up to 15 transmitters can be con nected wh...

Page 24: ...zero adjustment screw on the transmitter This is set to ENABLE when the instrument is shipped F0237 EPS ENTER EJA Ext SW mode Enable Enable Inhibit HELP SEND ESC ENTER Select Inhibit and press ENTER...

Page 25: ...s Write Protect status for 10 minutes While Write Protect status is released enter a new password in the New Password field It will not be possible to set a new password when 10 minutes have elapsed 2...

Page 26: ...select F0241 EPS ENTER EJA H2O Unit select 4C 4C 20C 68F HELP SEND ESC ENTER Select 20C 68F and press ENTER F4 Press SEND F2 to send data SEND 1 Device setup 4 Detailed setup 2 Signal condition 9 H2O...

Page 27: ...o low Operation is set in the Write Protect mode Value is set to a nearest possible value LRV set point is too high LRV set point is too low URV set point is too high URV set point is too low Set span...

Page 28: ...modify as needed Check URV and modify as needed Check SPAN and change as needed Readjust zero point Replace capsule Replace amplifier Check input Integral Indicator Display Description Cause Counterme...

Page 29: ...Pressure variable output variable 4 to 20 mA output variable Sensor temperature Static pressure Output in Engr unit Test output setting Self test Status Status of analog output alarm Write Protect En...

Page 30: ...emote seal Remote seal fill fluid Remote seal type Distributor Device type Device ID Final assembly number Universal revision Fld dev revision Software revision Model Style Lower range limit Upper ran...

Page 31: ...nts and the associated page numbers may not coincide with the one in old edition Add Hardware Write Protect and Burnout Direction with optional code F1 REVISION RECORD EPS 4th July 2000 ii 2 6 2 18 3...

Reviews: