C2-12
IM 34M06H62-02E
2nd Edition : June 2008-00
Rate-of-change Limit
The rate-of-change limit prevents drastic changes in the output by defining the maximum
rate of change allowed in the control output. This function is useful for protecting a
controlled load or machine.
For example, supposing that the rate-of-change is set to 2% per second, even if the PID
computation result changes instantly from 0 to 100%, the actual output changes linearly
from 0 to 100% over a duration of 50 s.
Figure C2.6 Rate-of-change Limit
Table C2.12 Rate-of-change Limit Parameter
Data Position Number
Symbol Description Unit
Data Range
Default
Value Attribute Stored
Loop 1 Loop 2 Loop 3 Loop 4
193 393 593 793 MVR
Rate-of-change
limit %/s
0: OFF
1 to 1000 (0.1 to 100.0% per second)
0 RW
The rate-of-change limit is disabled in the following situations:
-
When the Run/Stop Selection is set to Stop
-
When the Automatic/manual/cascade Selection is set to Manual
-
If burnout or AD converter error is detected when the Automatic/manual/cascade
Selection is set to Automatic (see Section C10, "Self-diagnosis Function")
-
When heating/cooling PID control is selected.
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...