C2-16
IM 34M06H62-02E
2nd Edition : June 2008-00
Dead Band
When a positive dead band value is specified, no heating and cooling output is generated
within the dead band.
Figure C2.8 Positive Dead Band (for P control)
When a negative dead band value is specified, both heating and cooling outputs are
generated and overlap within the dead band.
Figure C2.9 Negative Dead Band (for P control)
Table C2.15 Dead Band in Heating/Cooling PID Control
Data Position Number
Symbol Description
Unit Data
Range
Default
Value Attribute Stored
Loop 1 Loop 2 Loop 3 Loop 4
216 416 616 816 1.DB
Dead band
Industrial
unit
For PID control:
-10.0 to 10.0% of (PRH - PRL)
For ON/OFF control:
-50.0 to 50.0% of (PRH - PRL)
0 RW
236 436 636 836 2.DB
0 RW
256 456 656 856 3.DB
0 RW
276 476 676 876 4.DB
0 RW
Although the setting range of the dead band (DB) is
10.0% of (PRH - PRL), if a specified
value is beyond
(proportional band) (
PB), it is further limited to within
(PB) in PID
computation.