A2-7
IM 34M06H62-02E
3rd Edition : Jul.16, 2015-00
A2.5 Output
Specifications
Table A2.5 lists the output specifications of the F3CU04-0S and F3CU04-1S temperature
control and PID modules.
Table A2.5 Output Specifications
Item
Specification
F3CU04-0S
F3CU04-1S
Number of outputs
4
8
External power supply *
24 V DC
10%, 10 mA
24 V DC
10%, 250 mA
Time-proportional PID
output (open collector
output)
Rated load voltage
24 V DC
Maximum load current
0.1 A per point
0.1 A per point and 0.4 A for 8
points
ON residual voltage
0.5 V DC max.
OFF leakage current
0.1 mA max.
Response time
OFF
ON: 1 ms max., ON
OFF: 1 ms max.
Cycle time
0.5 to 240 s
Time-proportional
resolution
10 ms or 0.05% of F.S., whichever is greater
Continuous PID output
(analog output)
Output range
N.A.
4-20 mA (3.2-20.8 mA)
Allowable load
resistance
600
max.
Output accuracy
1.0% of F.S.
Output resolution
0.05% of F.S.
*
External power supply is not required if no output terminal is used (that is, if only input terminals are used).
A2.6 Backup
Function
The F3CU04-0S or F3CU04-1S temperature control and PID module provides a backup
function for storing input type, input range, set points and other parameter values, and
hence retaining their values even after power off and on. Parameters designated for
backup are stored whenever their corresponding registers are updated, provided the
backup function is not disabled. However, you need to execute a specific procedure
every time to back up set point values. Otherwise, stored set points will not be updated.
Even so, beware that set points will not be updated if the backup function is disabled.
Take note that there is a maximum limit to the number of write operations allowed for the
backup function.
Table A2.6 Backup Function
Description
Stored parameters
Controller parameters, I/O parameters, and operation parameters. For details, refer
to the list of registers.
Number of write
operations
Up to 100,000 write operations allowed
Disable backup function
This parameter disables the backup function. It may be used, if required, to avoid
reaching the maximum limit for write operations.
For details on the I/O data registers that are stored by the backup function and their data
position numbers, see Section B2, "Types of Relays and Registers."
In situations where the CPU module frequently overwrites the I/O data registers
earmarked to be stored by the backup function, the maximum limit for write operations
(100,000 times) may be reached. To prevent this, turn on the Disable Backup Function
parameter. Once the write limit is reached, data backup is no longer allowed and the
system enters hardware failure mode. Furthermore, parameter data may be reset at
system startup to the default values given in Section B2, "Types of Relays and
Registers."
Summary of Contents for F3CU04-0S
Page 2: ...Blank Page...
Page 18: ...Blank Page...
Page 32: ...Blank Page...
Page 34: ...Blank Page...
Page 50: ...Blank Page...
Page 90: ...Blank Page...
Page 118: ...Blank Page...
Page 130: ...Blank Page...
Page 204: ...Blank Page...
Page 222: ...Blank Page...
Page 224: ...Blank Page...
Page 228: ...Blank Page...
Page 230: ...Blank Page...
Page 232: ...Blank Page...
Page 234: ...Blank Page...
Page 240: ...Blank Page...
Page 242: ...Blank Page...
Page 254: ...Blank Page...
Page 258: ...Blank Page...
Page 260: ...Blank Page...