<Toc> <Ind>
<4. Module Access >
4-23
IM 34M6H54-01E
4.2.8
Output to Output Relays
The output relays used in the pulse input module are shown in Table 4.9.
Table 4.9
Output Relays Used in the Pulse Input Module
Output relay
number
Actions when on
Remarks
Y
uuu
33
Y
uuu
34
Y
uuu
35
Y
uuu
36
Y
uuu
37
Y
uuu
38
Y
uuu
39
Y
uuu
40
Y
uuu
41
Y
uuu
42
Y
uuu
43
Y
uuu
44
Y
uuu
45
Y
uuu
46
Y
uuu
47
Y
uuu
48
Y
uuu
49
Y
uuu
53
Y
uuu
57
Y
uuu
61
Actions performed
when changing
from off to on
Count operation
disabled with
output relay off.
Factory setting: Off
Resets input relay X
uuu
01 (or the external output terminal
selected by this state).
Resets input relay X
uuu
02 (or the external output terminal
selected by this state).
Resets input relay X
uuu
03 (or the external output terminal
selected by this state).
Resets counter of input channel 1.
Resets input relay X
uuu
05 (or the external output terminal
selected by this state).
Resets input relay X
uuu
06 (or the external output terminal
selected by this state).
Resets input relay X
uuu
07 (or the external output terminal
selected by this state).
Resets counter of input channel 2.
Resets input relay X
uuu
09 (or the external output terminal
selected by this state).
Resets input relay X
uuu
10 (or the external output terminal
selected by this state).
Resets input relay X
uuu
11 (or the external output terminal
selected by this state).
Resets counter of input channel 3.
Resets input relay X
uuu
13 (or the external output terminal
selected by this state).
Resets input relay X
uuu
14 (or the external output terminal
selected by this state).
Resets input relay X
uuu
15 (or the external output terminal
selected by this state).
Resets counter of input channel 4.
Enables count operation for input channel 1.
Enables count operation for input channel 2.
Enables count operation for input channel 3.
Enables count operation for input channel 4.
T0409.EPS
(Note) In situations where the count operation returns to 0 and stops, the count operation will be resumed by changing the
output relays Y
uuu
35, Y
uuu
39, Y
uuu
43, Y
uuu
47 from off to on (or in situations where the ring up-counter
exceeds the maximum value, the count operation will be resumed by resetting the input relay that turned on).
1st Edition : Feb.01,1999-00
Summary of Contents for F3XS04-3N
Page 2: ...Blank Page ...
Page 8: ...Blank Page ...
Page 10: ...Blank Page ...
Page 56: ...Blank Page ...
Page 66: ...Blank Page ...