3-20
IM 04L57B01-01EN
On/Off
Setup Item
Selectable Range or Options
Default Value
On/Off
Off/On
Off
On/Off
Select
On
to perform calibration correction on the GX70SM data.*
* This is fixed to Off for channels with data serial numbers assigned in communication channel
settings.
Mode
Setup Item
Selectable Range or Options
Default Value
Mode
Linearizer Approximation, Linearizer Bias, and
Correction factor
Off
Number of set points
*
2 to 12
2
* You can set this when the mode is not set to
Off
.
Mode
Set the correction type.
Number of set points
Set the number of points that make up the segments (including the start and end points).
1 to 12 (When the mode is set to linearizer approximation or
linearizer bias)*
Setup Item
Selectable Range or Options
Default Value
Linearizer input
-9999999 to 99999999
—
Linearizer output
-9999999 to 99999999
—
* The number of displayed points varies depending on the number of set points.
Linearizer input, Linearizer output
Enter the value of the set point. For linearizer input, set a value that is greater than the
previous value.
1 to 12 (When the mode is set to correction factor) (only for the /
AH option)*
Setup Item
Selectable Range or Options
Default Value
Uncorrected value
-9999999 to 99999999
—
Instrument correction factor
-9999999 to 99999999
—
Sensor correction factor
-9999999 to 99999999
—
* The number of displayed points varies depending on the number of set points.
Uncorrected value
Enter the uncorrected value. Set a value that is greater than the previous value.
Instrument correction factor
Set the instrument-dependent correction factor.
Sensor correction factor
Set the sensor-dependent correction factor.
3.4 Configuring the Settings for Wireless Input Unit Data