6-2
IM 04L57B01-01JA
6.1 Added and Changed Commands
Classification Category
Command
Description
Reference to the
Communication
Command IM
Changed
Setting
SHomeKind
Standard display [GX/GP]
Set the screen to display on the standard
display.
Wireless input unit info and wireless input unit
reconfiguration screens can be assigned to the
standard display.
2.4 Setting
Commands
SHomeKind
Setting
SFavoriteKind
Favorite screen [GX/GP]
Sets the favorite screen.
Wireless input unit info and wireless input unit
reconfiguration screens can be assigned to the
favorite screen.
2.4 Setting
Commands
SFavoriteKind
Setting
SMltMultiKind
Multi panel type
Sets the multi panel pattern for multi batch.
Wireless input unit info and wireless input unit
reconfiguration screens cannot be assigned to
the multi panel.
2.4 Setting
Commands
SMltMultiKind
Output
FData
Outputs the most recent channel data
Outputs the most recent I/O channel, math
channel, and communication channel data.
Wireless input unit data dropout (D) is added to
the alarm types.
2.5 Output
Commands
FData
Output
FFifoCur
Outputs channel FIFO data
Outputs the I/O channel, math channel, and
communication channel FIFO data.
Wireless input unit data dropout (D) is added to
the alarm types.
2.5 Output
Commands
FFifoCur
Output
FStat
Outputs the recorder status
Outputs the recorder status.
Wireless error detected is added to status
information 2.
2.5 Output
Commands
FStat
Output
FLog
Outputs the log
Outputs the alarm summary, message
summary, error log, etc.
Wireless input unit data dropout (D) is added to
the alarm types.
GX70SM operation is added to the detail event
log.
2.5 Output
Commands
FLog
Output
FEventLog
Outputs a Detail Event Log(/AS)
Outputs an event log. You can specify the
event, user, etc.
GX70SM operation is added to the detail event
log.
2.5 Output
Commands
FEventLog
Output
FCnf
Outputs setting data
The following commands are added to the
COMM category.
• SCalibUseCom
• SCalibCom
• SWUnitTimeOut
• SWUnitAutoMsg
The following commands are added to the
CALIB category.
• SCalibUseCom
• SCalibCom
2.5 Output
Commands
FCnf
Output
_OPT
Outputs the instrument’s option installation
information
Outputs the instrument’s option installation
information.
920 MHz wireless communication option (/
CM2, /CS2) is added to the instrument’s option
information.
2.8 Instrument
Information
Output
Commands
_OPT
Output
_UNS, _UNR
Outputs the Instrument’s Unit Configuration
Information
Outputs the instrument’s unit configuration
information.
/CM and /CS are added to the unit option
information output.
2.8 Instrument
Information
Output
Commands
_UNS or
_UNR