2

IM 77J08P01-01EN 1st Edition 

2017.10.30-00

1.3  Wall Mounting

Mount the converter onto the FRK panel as shown below or  

mount it directly on the wall.

 

FRK panel

1.4  DIN Rail Mounting

Place the converter so that the DIN rail fits into the upper part of 

the DIN-rail groove at the rear of the converter, and push until it 

clicks. The converter is fixed by a slide lock (at the lower part on 

the rear side of the converter).

To remove the converter, pull down the slide lock using a slotted 

screw-driver.

  

Slide lock

DIN rail

DIN rail groove

1.5 

Mounting Dimensions

Angle Mounting Dimensions

Mounting angle

M4×0.7 Mounting screw

Support

24.5

24.5

24.5 24.5 24.5

n×24.5+2

Unit: mm

73 90

Wall Mounting Dimensions

M4×0.7 Mounting screw

Unit: mm

24.5

24.5

24.5

24.5 24.5

90

2.  INSTALLATION LOCATION

 

z

Avoid the following environments for installation locations: 

Areas with vibration, corrosive gases, dust, water, oil, solvents, 

direct sunlight, radiation, a strong electric field, and/or a strong 

magnetic field, altitude of more than 2000m above sea level.

 

z

If there is any risk of a surge being induced into the power line 

and/or signal lines due to lightning or other factors, a dedicated 

lightning arrester should be used as protection for both this 

converter and a field-installed device.

 

z

Operating temperature/humidity range: 0 to 50ºC/5 to 90%RH 

(no condensation)

3.  EXTERNAL WIRING

 WARNING

Be sure to turn OFF the power supply before wiring to 

avoid the risk of electric shock. Use a tester or similar 

device to ensure that no power is being supplied to a 

cable to be connected

.

M4 screw terminals are provided for the connection of external 

signals. Attach a crimp-on lug to each wire for connection to the 

terminals.

 

z

Recommended cables: A nominal cross-sectional area of 0.5 

mm

2

 or thicker for signal cables, and that of 1.25 mm

2

 or thicker 

for power cables.

  

1

2

3

4

5

6

7

6
7

4
5

Output

Input

Power supply

1

2

3

1

2

2

3

Transmitter

Transmitter

Transmitter

PS+

+

+

+

PS+

+

When receiving 

current pulse by 

running a 

transmitter on an 

internal power 

supply

When receiving 

voltage pulse by 

running a 

transmitter on an 

internal power 

supply

When receiving 

non-voltage 

contact signal or 

voltage pulse

 CAUTION

●  This instrument may output a pulse when the power 

is turned on/off. Depending on the connected 

devices, this pulse output is counted as “one 

pulse.”

●  Do not connect anything to the terminals that are 

not used in the wiring diagram. Otherwise it may 

cause the malfunction or damage.

●  The power line and input/output signal lines should 

be installed away from noise-generating sources. 

Otherwise accuracy cannot be guaranteed.

●  Adhere strictly to the specifications to avoid 

overheating or damage. Before turning on the 

power, ensure the following:

(a) Power supply voltage and input signal value applied 

to the product should meet the required specifica

-

tions.

(b) The external wiring to the terminals are as specifica

-

tions.

●  Do not operate the product in the presence of 

flammable or explosive gases or vapors. 

●  The product is sensitive to static electricity; 

exercise  care in handling. Before you operate the 

product, touch a nearby metal part to discharge 

static electricity.