1. MOUNTING METHOD
CAUTION
●
Plug/disconnect the main unit into/from the
socket vertically to the socket face. Otherwise the
terminals may bend and it may cause bad contact.
●
The converter shall not tilt 5 degrees or more in
either direction when installed.
●
When the converter is not connected to the socket,
it is necessary to protect the socket against ingress
of dust to the connector part.
●
Keep this product in a conductive bag when
plugged out, during transport or storage.
1.1 Wall Mounting
Remove the stoppers (top and bottom) from the product and pull
out the main unit from the socket. Fix the socket on the wall using
two M4 screws. Next, insert the main unit into the socket and
fasten the main unit with the stoppers (top and bottom).
5 or more
(51)
(85)
Socket
Socket
Stopper
Mounting screws
Mounting Dimensions
Unit: mm
40±0.2
Pitch: 56 or more
2-ø4.5 or
2-M4
Note:
(1) More than 5 mm interval is
required for side-by-side
close mounting.
(2) Use the supplied spacer for
DIN rail mounting to keep 5
mm interval.
Main unit
1.2 DIN Rail Mounting
Insert a DIN rail into the upper part of the DIN rail groove on the
rear of the socket, and then slide the slide lock at the lower part of
the socket upwards until the socket is fixed into position as shown
below.
Slide lock
Spacer
DIN rail
DIN rail
Fit into here
Push
(Rear of the socket)
1.3 Using a Duct
When using a wiring duct, install the duct at leaset 20 mm away
from the top and bottom faces of the main unit.
2. INSTALLATION LOCATIONS
• Avoid the following environments for installation locations:
Areas with vibrations, corrosive gases, dust, water, oil,
solvents, direct sunlight, radiation, a strong electric field,
and/or a strong magnetic field, direct radiant heat, wind,
temperature fluctuation, 2000 m or more above sea level.
• If there is any risk of a surge being induced into the power
line and/or signal lines due to lightning or other factors, a
dedicated lightning arrester should be used as protection for
both this unit and a field-installed device.
• Operating temperature/humidity range: 0 to 50°C (0 to 40 °C
for multiple mounting)/5 to 90%RH (no condensation)
* If the previous model (style S3.xx earlier) is installed
together, the ambient temperature is 0 to 40°C.
• Continuous vibration: (at 5 to 9 Hz) Half amplitude of 3 mm or
less (at 9 to 150 Hz) 9.8m/s
2
or less, 1 oct/min for 90 minutes
each in the three axis directions
• Impact: 98 m/s
2
or less, 11 ms, 3 axes, 6 directions, 3 times
each
• Install in a place where rigidity is secured.
3. EXTERNAL WIRING
WARNING
●
To avoid the risk of an electric shock, turn off the
power supply and use a tester or similar device to
ensure that no power is supplied to a cable to be
connected, before carrying out wiring work.
●
Do not operate the product in the presence of
flammable or explosive gases or vapors. To do so is
highly dangerous.
●
Use of the product ignoring the specifications may
cause overheating or damage. Before turning on
the power, ensure the following:
• Power supply voltage and input signal value
applied to the product should meet the required
specifications.
• The external wiring to the terminals and wiring to
ground are as specifications.
Wiring should be connected to the terminals on the socket
of the product. The terminals for external connections are of
M3.5 screws. Use crimp-on terminal lugs for connections to the
terminals.
• Recommended cables: A nominal cross-sectional area of
0.5 mm
2
or thicker for signal cables, and that of 1.25 mm
2
or
thicker for power cables.
6 5
4 3
7 8
1 2
L+
N–
GND
3
4
+
–
1
2
+
–
6
7
8
Ri
Power Supply
Output
Input signal
Receivingl resistor
for current input
Ri: External receiving resistor
for current input
(See the table below.)
<External Receiving Resistor for Current Input>
Input ragne Resistance Part No.
Input ragne Resistance Part No.
10 to 50 mA DC 100 Ω RES-100 2 to 10 mA DC 500 Ω RES-500
4 to 20 mADC
250 Ω RES-250
0 to 10 mA DC
0 to 20 mADC
1 to 5 mA DC
1k Ω RES-01K
0 to 16 mADC
0 to 1 mA DC
CAUTION
●
The power line and input/output signal lines should
be installed away from noise-generating sources.
Other wise accuracy cannot be guaranteed.
●
Make sure to earth ground the ground terminal
through minimum resistance. The length and
thickness of the grounding cable should be as
short and thick as possible. Directly connect the
lead from the ground terminal (terminal no. 6) of
the product to the ground. Do not carry out daisy-
chained inter-ground terminal wiring.
2
IM 77J04H01-01E 3rd Edition June 29, 2018-00