3

7.  SWITCHING PARAMETERS

 CAUTION

 

If the alarm action (AL1 to AL4) is set to "OFF," the relevant alarm setpoint (A1 to A4) 

is not displayed.

 

If no keystroke is made for more than 2 minutes, the PV screen automatically 

appears, regardless of the parameter displayed. In this case, if a data change is in 

progress (the decimal point is blinking), the data being changed becomes invalid and 

the PV screen appears with the previous data displayed as is. However, this action 

does not take place if the parameter "MAN", "ZER" or "SPN" is being displayed.

Operation Parameter Screen

Setup Parameter Screen 1

Setup Parameter Screen 2

To the Operation Parameter Screen

AA

AA

AA

Press this key for more than 3 sec.

Press this key

for more than 3 sec.

Press this key 

for more than 3 sec.

A

is displayed when the PV display color mode (PCM) has 

been set to 6, 7, 8 or 9. 

A

E

E

D

C

B

C

D

D

C

E

or

Press the DOWN key to display "-1" 

on the DATA display and then press 

the SET/ENT key.

Power 

ON

Displays a measured value (scaling value). 

In this manual, this screen is called the "PV 

(measured value) screen." 

Alarm-1 setpoint (A1)

Sets the alarm-1 setpoint.

Alarm-2 setpoint (A2)

Sets the alarm-2 setpoint.

Alarm-3 setpoint (A3)

(Displayed only for 4 points of alarms) 

Sets the alarm-3 setpoint.

Alarm-4 setpoint (A4)

(Displayed only for 4 points of alarms) 

Sets the alarm-4 setpoint.

Alarm-1 action (AL1)

Sets the direction of alarm-1 action. 

Range code No. (IN)

Sets the range code number (input type). 

Maximum measured input value (RH)

Sets the maximum value of the measured 

input range (100%).

Minimum measured input value (RL)

Sets the minimum value of the measured 

input range (0%).

Decimal point position of scaling value (SDP)

Sets the position of the decimal point of the 

input scaling value (displayed value). 

Maximum input scaling value (SH)

This parameter is set to display any value as 

the maximum measured input value in the 

PV display.

Minimum input scaling value (SL)

This parameter is set to display any value as 

the minimum measured input value in the PV 

display. 

Measured input bias (BS)

This parameter is set to correct a measured 

input value.

PV display color mode (PCM)

Sets the Active color PV display.

Economical mode time (ECO)

This parameter is set to extinguish the display 

(not including the READY and alarm lamps) if no 

keystroke is made for a specified time. 

Input adjustment reset (RST)

Used to reset an input adjustment value. 

Input adjustment point LOW (BL)

Sets the reference value corresponding to 

0% of the input when an input adjustment is 

made.

Input adjustment LOW (AL)

Adjusts the 0% value of an input.

Input adjustment point HIGH (BH)

Sets the reference value corresponding to 

100% of the input when an input adjustment 

is made.

Input adjustment HIGH (AH)

Adjusts the 100% value of an input.

Alarm-2 action (AL2)

Sets the direction of alarm-2 action.

Alarm-3 action (AL3)

(Displayed only for 4 points of alarms) 

Sets the direction of alarm-3 action.

Alarm-4 action (AL4)

(Displayed only for 4 points of alarms) 

Sets the direction of alarm-4 action.

Alarm-1 hysteresis (HY1)

Sets the hysteresis of alarm 1.

Alarm-2 hysteresis (HY2)

Sets the hysteresis of alarm 2. 

Alarm-3 hysteresis (HY3)

(Displayed only for 4 points of alarms) 

Sets the hysteresis of alarm 3.

Alarm-4 hysteresis (HY4)

(Displayed only for 4 points of alarms) 

Sets the hysteresis of alarm 4. 

Alarm ON delay (OND)

Sets the condition monitoring time from the 

establishment of alarm conditions to its 

output. *        is displayed for MVHK-2 (FAIL 

output type).

Alarm OFF delay (OFD)

Sets the condition monitoring time from the 

establishment of return-to normal conditions 

to its output. *        is displayed for MVHK-2 (FAIL 

output type).

Setpoint (SP)

When using a deviation alarm, this 

parameter is set to the value treated as the 

reference for deviations. 

Key lock (LOC)

This parameter is set when change of parameter 

settings (all parameters or parameters other than the 

operation parameters) is locked to prevent wrong 

operations.

Visibility of monitor output adjustment screen (MON)

Sets the visibility of the screen for adjusting monitor 

output.  Pressing the SET/ENT key with "ON" 

displayed on the DATA display causes the 

adjustment screen to appear.

Forced output of a monitor output value (MAN)

Used to force a value equivalent to -25% to +125% 

of an analog output value to output, regardless of 

input.

Monitor output zero adjustment (ZER

)

Adjusts the zero point of the monitor output. 

Monitor output span adjustment (SPN

)

Adjusts the span of the monitor output. 

Maximum monitor output value (RTH)

This parameter is set to treat any value as 

the maximum output value with respect to 

the input scaling value.

High limit for PV display color change (PCH)

Sets the high limit for PV limit mode or SP 

deviation mode of Active color PV display.

Low limit for PV display color change (PCL)

Sets the low limit for PV limit mode or SP 

deviation mode of Active color PV display.

Minimum monitor output value (RTL)

This parameter is set to treat any value as 

the minimum output value with respect to the 

input scaling value. 

Communication protocol (PSL)

Sets the communication protocol.

Communication address (ADR)

Sets the communication address. 

Baud rate (BPS)

Sets the baud rate. 

Parity (PRI)

Sets the parity.

Stop bit (STP)

Sets the stop bit.

Data length (DLN)

Sets the data length. 

Chapter 8

Chapter 8

Chapter 8

Chapter 8

Chapter 8

Chapter 8

Chapter 12

Chapter 12

Chapter 11

Chapter 10

Chapter 10

Chapter 10

Chapter 10

Chapter 10

Relay specification display (RLY)

The relay specification (NO or NC) of alarm 

output 1, alarm output 2, FAIL output is 

displayed. * Only MVHK-2 (FAIL output type) 

is displayed.

Chapter 12

Section 13.1

Section 13.1

Section 13.1

Section 13.1

Section 13.1

Section 13.1

Section 13.2

Section 13.2

Section 13.2

Section 13.2

Section 13.2

Section 13.2

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Alarm 1 ON delay (ON1)

Set the condition monitoring time from alarm 

condition establishment of alarm 1 to output.

Alarm 1 OFF delay (OF1)

Set the condition monitoring time from the 

return to normal conditions of alarm 1 to the 

output.

Alarm 2 OFF delay (OF2)

Set the condition monitoring time from the 

return to normal conditions of alarm 2 to the 

output.

Chapter 9

Alarm 2 ON delay (ON2)

Set the condition monitoring time from alarm 

condition establishment of alarm 2 to output.

Chapter 9

Chapter 9

Chapter 9

Chapter 12

To the Setup Parameter Screen 1

To the Operation Parameter Screen 

Chapter 9

To the Setup Parameter Screen 2

B

B

is displayed when the monitor output (analog) has been 

specified. 

     is displayed when the 

monitor output (RS-485 

communication) has been 

specified.

The 

symbol indicates a reference chapter/section in this manual.

A

Chapter 11

Chapter 11

         is displayed 

when the monitor 

output (analog) has 

been specified. 

Summary of Contents for JUXTA MVHK

Page 1: ...O F3 Alarm 1 NO Alarm 2 NC Fail output NO F4 Alarm 1 NC Alarm 2 NC Fail output NO F5 Alarm 1 NO Alarm 2 NO Fail output NC F6 Alarm 1 NC Alarm 2 NO Fail output NC F7 Alarm 1 NO Alarm 2 NC Fail output N...

Page 2: ...UNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage Fail output type 1 PV measured value display Place for adhering the tag number...

Page 3: ...ysteresis of alarm 4 Alarm ON delay OND Sets the condition monitoring time from the establishment of alarm conditions to its output is displayed for MVHK 2 FAIL output type Alarm OFF delay OFD Sets th...

Page 4: ...isplay 1 Continue to the upper right Press the SET ENT key to accept the data as is because the initial value for the range code No 97 is 20 00 The next parameter RL appears because no data has been c...

Page 5: ...play 0 Press Continue to the upper right Press the UP or DOWN key to display 5 on the DATA display Press the SET ENT key to accept alarm 1 hysteresis 5 Press the SET ENT key to display parameter OND T...

Page 6: ...t alarm status red 5 Link to alarm 1 and alarm 2 under normal condition red at alarm status green 6 PV limit when more than PCL less than PCH green when PCL or less PCH or more red 7 PV limit when mor...

Page 7: ...ange code No 97 Measured input range Input scaling value Input range of settings for MVHK range code No 97 Maximum measured input value 20 00 mA Minimum measured input value 4 00 mA Maximum input scal...

Page 8: ...3 2 1 Setting Ranges and Factory Set Values of Monitor Output Communication Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Communication pr...

Reviews: