8. SETTING INPUT-RELATED PARAMETERS
8.1 Input Scaling
The MVHK allows you to set any input scaling value (displayed value) with respect to the
measured input range.
For example, if the MVHK measured input range is 4 to 20 mA DC, setting the input scaling range
(displayed value) to -50 to 150 causes the MVHK to display “0” in the PV display at 8 mA input
(equivalent to 25% of 4 to 20 mA input) as shown in the figure below.
Range code No. 97
Measured input range
Input scaling value
Input range when the MVHK
range code No. is 97
Maximum value of measured
input range: 20.00 mA
Minimum value of measured
input range: 4.00 mA
Maximum input scaling
value: 150
Minimum input scaling
value: -50
At 8 mA input, "0" is displayed on
the PV display.
20 mA
20 mA
(RH)
150
(SH)
0 mA
4 mA
(RL)
8 mA
-50
(SL)
8.2 Setting Ranges and Factory-Set Values of Input-Related Parameters
Setup Parameter Screen 2
Parameter
Symbol
Parameter Name
Setting Range
Factory-Set
Value
Range code No.
(IN)
Range code
No.
Instrument input range
Receiving
resistor
−10.00 to +10.00 V DC
−5.00 to +5.00 V DC
−1.000 to +1.000 V DC
0.00 to 50.00 mA DC
100 Ω
0.00 to 10.00 mA DC
100 Ω
0.00 to 20.00 mA DC
250 Ω
0.000 to 4.000 mA DC
250 Ω
92 *
1
Maximum measured
input value (RH)
RL + 1 digit to the max. value of instrument input range
5.00 *
1
Minimum measured input
value (RL)
Min. value of instrument input range to RH - 1 digit
-5.00 *
1
Decimal point position of
scaling value (SDP)
0 (no decimal place), 1 (one decimal place), 2 (two decimal
places), 3 (three decimal places)
1
Maximum input scaling
value (SH)
SL + 1 digit to 9999
* The setting range depends on the setting of the decimal point position
(SDP).
100.0
Minimum input scaling
value (SL)
-1999 to SH - 1 digit
* The setting range depends on the setting of the decimal point position
(SDP).
0.0
*1 The factory-set values for the input signal code “6” are as follows:
Range code No.: 92; maximum measured input value: 5.00; and minimum measured input value: 1.00
The factory-set values for the input signal code “A” are as follows:
Range code No.: 97; maximum measured input value: 20.00; and minimum measured input value: 4.00
8.3 Setting Input-Related Parameters
This section describes an example of setting the range code No. (IN) to “97,” measured
input range (RL, RH) to “4 to 20 mA DC,” the decimal point position of input scaling value (SDP) to
“0” (with no decimal place) and input scaling values (SL, SH) to “-50 to 150.”
CAUTION
Note that setting the range code No. (IN) to a value other than those specified in Section
8.2 is invalid.
Press .
Press .
Press .
When you press the SET/ENT key for more than 3 sec. with the
Operation Parameter Screen displayed, the Setup Parameter
Screen 1 appears.
When the power is turned on, the PV screen of the Operation
Parameter Screen appears.
Press the UP or DOWN key to display "97" on the DATA display.
Press the SET/ENT key to accept range code No. "97."
Press the SET/ENT key again to display parameter "RH."
Press this key for
more than 3 sec.
This completes the process for
setting the range code No.
The decimal point blinks during
data change.
Press the SET/ENT key to display parameter "LOC."
Press the DOWN key to display "-1" on the DATA display.
Press the SET/ENT key to display parameter "IN" in the Setup
Parameter Screen 2.
Setup Parameter Screen 1
Setup Parameter Screen 2
Operation Parameter Screen
Power ON
Step 1
Setting the range code
The decimal point blinks during
data change.
Press or
to display "97."
Press to display "LOC."
Press to display "-1."
Continue to the upper right
Press the SET/ENT key to accept the data as is, because the
initial value for the range code No. 97 is "20.00." (The next
parameter "RL" appears because no data has been changed.)
Press the UP key to display "4.00" on the DATA display.
Press the SET/ENT key to accept this data.
Press the SET/ENT key again to display parameter "SDP."
Press the DOWN key to display "0" on the DATA display.
Press the SET/ENT key to accept this data.
Press the SET/ENT key again to display parameter "SH."
Press the UP key to display "150" on the DATA display.
Press the SET/ENT key to accept this data.
Press the SET/ENT key again to display parameter "SL."
Press the DOWN key to display "-50" on the DATA display.
Press .
Press .
This completes the process for
setting the max. measured input
value.
This completes the process for
setting the minimum measured
input value.
This completes the process for
setting the decimal point
position.
This completes the process for
setting the maximum input
scaling value.
This completes the process for
setting the minimum input
scaling value.
Press to display "4.00."
Press to display "0."
The decimal point blinks during
data change.
The decimal point blinks during
data change.
The decimal point blinks during
data change.
The decimal point blinks during
data change.
To the Operation Parameter Screen
Setting the max. and min. measured input values
Setting the max. and min. input scaling values
Setting the decimal point position
Step 2
Press because the
data remains the same.
Press .
Press .
Press to display "150."
Press .
Press .
Press to display "-50."
Press .
Press for more than
3 sec.
Press the SET/ENT key to accept this data.
Press the SET/ENT key for more than 3 sec.
This causes the Operation Parameter Screen to appear.
9. SETTING ALARM-RELATED PARAMETERS
9.1 Setting Ranges and Factory-Set Values of Alarm-Related Parameters
Operation Parameter Screen
Parameter
Symbol
Parameter Name
Setting Range
Factory-Set Value
Alarm-1 setpoint
(A1)
-1999 to 9999
(Within the range of set input scaling values)
* The setting range depends on the setting of the decimal
point position (SDP).
20.0
Alarm-2 setpoint
(A2)
2 points of alarms: 80.0
4 points of alarms: 30.0
Alarm-3 setpoint
(A3)
70.0
Alarm-4 setpoint
(A4)
80.0
Setup Parameter Screen 2
Parameter
Symbol
Parameter Name
Setting Range
Factory-Set Value
Alarm-1 action
(AL1)
See the Alarm Action Type Codes table.
2
Alarm-2 action
(AL2)
2 points of alarms: 1
4 points of alarms: 2
Alarm-3 action
(AL3)
1
Alarm-4 action
(AL4)
1
Alarm-1 hysteresis
(HY1)
0 to 9999
The value resulting from adding a hysteresis value to an
alarm setpoint should be within the range of set input
scaling values.
* The setting range depends on the setting of the decimal
point position (SDP).
Note: When parameter settings are initialized, it is set to 3%
of the scaling span.
1.0
Alarm-2 hysteresis
(HY2)
1.0
Alarm-3 hysteresis
(HY3)
1.0
Alarm-4 hysteresis
(HY4)
1.0
Alarm ON delay
(OND)
Setting range: 0 to 999 sec.
Setting resolution: 1 sec.
* For MVHK-2 (FAIL output type), ON1 and ON2 are
displayed.
0
Alarm OFF delay
(OFD)
Setting range: 0 to 999 sec.
Setting resolution: 1 sec.
* For MVHK-2 (FAIL output type), OF1 and OF2 are
displayed.
0
Alarm 1 ON delay
(ON1)
Setting range: 0 to 999 sec.
Setting resolution: 1 sec.
* Only MVHK-2 (FAIL output type) is displayed. Refer to
OND for setting operation.
0
Alarm 2 ON delay
(ON2)
0
Alarm 1 OFF delay
(OF1)
Setting range: 0 to 999 sec.
Setting resolution: 1 sec.
* Only MVHK-2 (FAIL output type) is displayed. Refer to
OFD for setting operation.
0
Alarm 2 OFF delay
(OF2)
0
Setpoint (SP)
-1999 to 9999
Within the range of set input scaling values
* The setting range depends on the setting of the decimal
point position (SDP).
0.0