IM 77J04H31-01E 4th Edition 

Oct. 15, 2019-00

4

8.  SETTING INPUT-RELATED PARAMETERS 

8.1  Input Scaling 

The MVHK allows you to set any input scaling value (displayed value) with respect to the 

measured input range. 

For example, if the MVHK measured input range is 4 to 20 mA DC, setting the input scaling range 

(displayed value) to -50 to 150 causes the MVHK to display “0” in the PV display at 8 mA input 

(equivalent to 25% of 4 to 20 mA input) as shown in the figure below. 

 

Range code No. 97 

Measured input range

Input scaling value

Input range when the MVHK 

range code No. is 97

Maximum value of measured 

input range: 20.00 mA 

Minimum value of measured 

input range: 4.00 mA 

Maximum input scaling 

value: 150 

Minimum input scaling 

value: -50

At 8 mA input, "0" is displayed on 

the PV display. 

20 mA

20 mA

(RH)

150

(SH)

0 mA

4 mA

(RL)

8 mA

-50

(SL)

8.2  Setting Ranges and Factory-Set Values of Input-Related Parameters

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

Range code No.

(IN)

Range code  

No.

Instrument input range

Receiving

resistor

−10.00 to +10.00 V DC

−5.00 to +5.00 V DC

−1.000 to +1.000 V DC

0.00 to 50.00 mA DC

100 Ω

0.00 to 10.00 mA DC

100 Ω

0.00 to 20.00 mA DC

250 Ω

0.000 to 4.000 mA DC

250 Ω

92 *

1

Maximum measured 

input value (RH)

RL + 1 digit to the max. value of instrument input range

5.00 *

1

Minimum measured input 

value (RL) 

Min. value of instrument input range to RH - 1 digit 

-5.00 *

1

Decimal point position of 

scaling value (SDP) 

0 (no decimal place), 1 (one decimal place),  2 (two decimal 

places), 3 (three decimal places) 

1

Maximum input scaling 

value (SH)

SL + 1 digit to 9999

*  The setting range depends on the setting of the decimal point position 

(SDP). 

100.0

Minimum input scaling 

value (SL)

-1999 to SH - 1 digit 

*  The setting range depends on the setting of the decimal point position 

(SDP). 

0.0

*1  The factory-set values for the input signal code “6” are as follows: 

 

Range code No.: 92; maximum measured input value: 5.00; and minimum measured input value: 1.00 

 

The factory-set values for the input signal code “A” are as follows: 

 

Range code No.: 97; maximum measured input value: 20.00; and minimum measured input value: 4.00

8.3  Setting Input-Related Parameters 

This section describes an example of setting the range code No. (IN) to “97,” measured 

input range (RL, RH) to “4 to 20 mA DC,” the decimal point position of input scaling value (SDP) to 

“0” (with no decimal place) and input scaling values (SL, SH) to “-50 to 150.” 

 CAUTION 

Note that setting the range code No. (IN) to a value other than those specified in Section 

8.2 is invalid. 

Press .

Press .

Press .

When you press the SET/ENT key for more than 3 sec. with the 

Operation Parameter Screen displayed, the Setup Parameter 

Screen 1 appears. 

When the power is turned on, the PV screen of the Operation 

Parameter Screen appears. 

Press the UP or DOWN key to display "97" on the DATA display. 

Press the SET/ENT key to accept range code No. "97." 

Press the SET/ENT key again to display parameter "RH."

Press this key for 

more than 3 sec.

This completes the process for 

setting the range code No.

The decimal point blinks during 

data change.

Press the SET/ENT key to display parameter "LOC." 

Press the DOWN key to display "-1" on the DATA display. 

Press the SET/ENT key to display parameter "IN" in the Setup 
Parameter Screen 2. 

Setup Parameter Screen 1

Setup Parameter Screen 2

Operation Parameter Screen

Power ON

Step 1

Setting the range code 

The decimal point blinks during 

data change.

Press                 or           
to display "97."

Press              to display "LOC." 

Press             to display "-1." 

Continue to the upper right

Press the SET/ENT key to accept the data as is, because the 

initial value for the range code No. 97 is "20.00." (The next 

parameter "RL" appears because no data has been changed.) 

Press the UP key to display "4.00" on the DATA display. 

Press the SET/ENT key to accept this data. 

Press the SET/ENT key again to display parameter "SDP." 

Press the DOWN key to display "0" on the DATA display. 

Press the SET/ENT key to accept this data. 

Press the SET/ENT key again to display parameter "SH."

Press the UP key to display "150" on the DATA display. 

Press the SET/ENT key to accept this data. 

Press the SET/ENT key again to display parameter "SL."

Press the DOWN key to display "-50" on the DATA display.

Press               .

Press               .

This completes the process for 

setting the max. measured input 

value. 

This completes the process for 

setting the minimum measured 

input value.

This completes the process for 

setting the decimal point 

position.

This completes the process for 

setting the maximum input 

scaling value. 

This completes the process for 

setting the minimum input 

scaling value. 

Press               to display "4.00."

Press               to display "0." 

The decimal point blinks during 

data change.

The decimal point blinks during 

data change.

The decimal point blinks during 

data change. 

The decimal point blinks during 

data change. 

To the Operation Parameter Screen

Setting the max. and min. measured input values

Setting the max. and min. input scaling values

Setting the decimal point position

Step 2

Press               because the 
data remains the same. 

Press                . 

Press                . 

Press                to display "150." 

Press                . 

Press                . 

Press                to display "-50." 

Press                . 

Press                for more than

 

 

         3 sec. 

Press the SET/ENT key to accept this data. 

Press the SET/ENT key for more than 3 sec.

This causes the Operation Parameter Screen to appear.

9.  SETTING ALARM-RELATED PARAMETERS 

9.1  Setting Ranges and Factory-Set Values of Alarm-Related Parameters

Operation Parameter Screen

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set Value

Alarm-1 setpoint 

(A1)

-1999 to 9999

(Within the range of set input scaling values)

*  The setting range depends on the setting of the decimal 

point position (SDP).

20.0

Alarm-2 setpoint 

(A2)

2 points of alarms: 80.0

4 points of alarms: 30.0

Alarm-3 setpoint 

(A3)

70.0

Alarm-4 setpoint 

(A4)

80.0

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set Value

Alarm-1 action 

(AL1)

See the Alarm Action Type Codes table.

2

Alarm-2 action 

(AL2)

2 points of alarms: 1

4 points of alarms: 2

Alarm-3 action 

(AL3)

1

Alarm-4 action 

(AL4)

1

Alarm-1 hysteresis 

(HY1)

0 to 9999

The value resulting from adding a hysteresis value to an 

alarm setpoint should be within the range of set input 

scaling values.

*  The setting range depends on the setting of the decimal 

point position (SDP).

Note:  When parameter settings are initialized, it is set to 3% 

of the scaling span.

1.0

Alarm-2 hysteresis 

(HY2)

1.0

Alarm-3 hysteresis 

(HY3)

1.0

Alarm-4 hysteresis 

(HY4)

1.0

Alarm ON delay 

(OND)

Setting range: 0 to 999 sec. 

Setting resolution: 1 sec.

*  For MVHK-2 (FAIL output type), ON1 and ON2 are 

displayed.

0

Alarm OFF delay 

(OFD)

Setting range: 0 to 999 sec. 

Setting resolution: 1 sec.

*  For MVHK-2 (FAIL output type), OF1 and OF2 are 

displayed.

0

Alarm 1 ON delay 

(ON1)

Setting range: 0 to 999 sec. 

Setting resolution: 1 sec.

*  Only MVHK-2 (FAIL output type) is displayed. Refer to 

OND for setting operation.

0

Alarm 2 ON delay 

(ON2)

0

Alarm 1 OFF delay 

(OF1)

Setting range: 0 to 999 sec. 

Setting resolution: 1 sec.

*  Only MVHK-2 (FAIL output type) is displayed. Refer to 

OFD for setting operation.

0

Alarm 2 OFF delay 

(OF2)

0

Setpoint (SP)

-1999 to 9999

Within the range of set input scaling values

*  The setting range depends on the setting of the decimal 

point position (SDP).

0.0

Summary of Contents for JUXTA MVHK

Page 1: ...O F3 Alarm 1 NO Alarm 2 NC Fail output NO F4 Alarm 1 NC Alarm 2 NC Fail output NO F5 Alarm 1 NO Alarm 2 NO Fail output NC F6 Alarm 1 NC Alarm 2 NO Fail output NC F7 Alarm 1 NO Alarm 2 NC Fail output N...

Page 2: ...UNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage Fail output type 1 PV measured value display Place for adhering the tag number...

Page 3: ...ysteresis of alarm 4 Alarm ON delay OND Sets the condition monitoring time from the establishment of alarm conditions to its output is displayed for MVHK 2 FAIL output type Alarm OFF delay OFD Sets th...

Page 4: ...isplay 1 Continue to the upper right Press the SET ENT key to accept the data as is because the initial value for the range code No 97 is 20 00 The next parameter RL appears because no data has been c...

Page 5: ...play 0 Press Continue to the upper right Press the UP or DOWN key to display 5 on the DATA display Press the SET ENT key to accept alarm 1 hysteresis 5 Press the SET ENT key to display parameter OND T...

Page 6: ...t alarm status red 5 Link to alarm 1 and alarm 2 under normal condition red at alarm status green 6 PV limit when more than PCL less than PCH green when PCL or less PCH or more red 7 PV limit when mor...

Page 7: ...ange code No 97 Measured input range Input scaling value Input range of settings for MVHK range code No 97 Maximum measured input value 20 00 mA Minimum measured input value 4 00 mA Maximum input scal...

Page 8: ...3 2 1 Setting Ranges and Factory Set Values of Monitor Output Communication Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Communication pr...

Reviews: