background image

IM 77J04H31-01E 4th Edition 

Oct. 15, 2019-00

5

<Alarm Action Type Codes>

Alarm 

Type

Alarm Action

Alarm Action Type Code

Without Stand-by 

Action

With Stand-by 

Action

Deenergized 

under 

Normal 

Condition

Energized 

under 

Normal 

Condition

Deenergized 

under 

Normal 

Condition

Energized 

under 

Normal 

Condition

PV high-

limit alarm

Hysteresis

Alarm

Alarm setpoint

Normal

PV

PV low-limit 

alarm

PV

Hysteresis

Normal

Alarm setpoint

Alarm

Deviation 

high-limit 

alarm

PV

Hysteresis

Alarm

Setpoint Deviation setpoint

Normal

Deviation 

low-limit 

alarm

PV

Hysteresis

Normal

Setpoint

Deviation setpoint

Alarm

Deviation 

high and 

low-limit 

alarm

PV

Hysteresis

Hysteresis

Setpoint Deviation setpoint

Deviation setpoint

Alarm

Normal 

Alarm

Deviation 

within high 

and low-

limit alarm

PV

Hysteresis

Hysteresis

Setpoint Deviation setpoint

Deviation setpoint

Alarm

Normal

Normal

No alarm

(Parameters A1 to A4 are not displayed.)

Low-limit 

alarm 

setpoint

Power ON

PV

Time

Normal

Regarded 

as normal

Abnormal

(Alarm ON)

If an alarm type code with 
stand-by action is set, alarm 
action is turned off during the 
start-up control. 
This function is useful at power 
ON or when changing the alarm  
type.

Stand-by Action

9.2  Setting Alarm Output-Related Parameters 

This section describes an example of setting the alarm-1 action (AL1) to “12” (PV low-limit alarm, with 

stand-by action), alarm-1 setpoint (A1) to “0,” alarm-1 hysteresis (HY1) to “5,” alarm ON delay (OND) 

to “5” and alarm OFF delay (OFD) to “5” with the input scaling values (SL, SH) set to “-50 to 150.” 

(Parameters relating to alarm 2 to alarm 4 can be set in the same way as the procedure below.) 

The alarm setpoints, setpoint (set when setting a deviation alarm) and hysteresis are based on the 

set input scaling values. 

For example, if the input scaling values are “-50 to 150,” to set the low-limit alarm value to 25% of the 

measured input range, set the low-limit alarm value to “0.” 

Press            or          
to display "12."

When the SET/ENT key is pressed for more than 3 sec. 

with the Operation Parameter Screen displayed, the Setup 

Parameter Screen 1 appears with parameter "AL1" 

displayed.

To the Setup Parameter 

Screen 1

When the power is turned on, the PV screen of the 

Operation Parameter Screen appears. 

Press            for more 

 

        than 3 sec. 

Press            . 

This completes the process for 

setting the alarm-1 action. 

This completes the process for 

setting the alarm-1 setpoint.  

The decimal point blinks during 

data change.

The decimal point blinks during 

data change. 

Press the UP or DOWN key to display "12" on the DATA 

display. 

Press the SET/ENT key to accept alarm-1 action "12." 

Then to set the alarm setpoint, press the SET/ENT key for 

more than 3 sec. to display the Operation Parameter 

Screen.   (To set the hysteresis parameter and successive 

settings, press the SET/ENT key to display the next 

parameter.) 

Setup Parameter Screen 1

Operation Parameter Screen

Press the SET/ENT key to display parameter "A1." 

Press the UP or DOWN key to display a low-limit alarm 

value "0" (value corresponding to 25% of the scaling 

value) that is set to the DATA display. 

Press the SET/ENT key to accept low-limit alarm "0." 

Operation Parameter Screen 

Power ON

Step 3

Setting the alarm action

Setting the alarm setpoint

Press this key for 

more than 3 sec.

Press            to display "A1." 

Press            or            
to display "0." 

Press            . 

Continue to the upper right

Press the UP or DOWN key to display "5" on the DATA 

display. 

Press the SET/ENT key to accept alarm-1 hysteresis "5." 

Press the SET/ENT key to display parameter "OND." 

This completes the process for 

setting the alarm-1 hysteresis. 

The decimal point blinks during 

data change.

Press the UP or DOWN key to display "5" (sec.) on the 

DATA display. 

Press the SET/ENT key to accept alarm ON delay "5" 

(sec). 

Press the SET/ENT key again to display parameter 

"OFD." 

The decimal point blinks during 

data change. 

Press the UP or DOWN key to display "5" (sec.) on the 

DATA display. 

Press the SET/ENT key to accept alarm OFF delay "5" 

(sec). 

Press the SET/ENT key for more than 3 sec.

This causes the Operation Parameter Screen to appear. 

This completes the process for 

setting the alarm OFF delay. 

The decimal point blinks during 

data change. 

Setup Parameter Screen 1

To the Operation Parameter Screen

Setting the hysteresis

Setting the alarm ON delay

Setting the alarm OFF delay

Press             to display 
"OND." 

Press            . 

Press            or  
to display "5." 

Press            or            
to display "5." 

Press            .

Press            .

Press            or            
to display "5."

Press            .

Press            for more 

 

          than 3 sec.

This completes the process for 

setting the alarm ON delay.

10.  INPUT ADJUSTMENTS 

10.1 Setting Ranges and Factory-Set Values of Adjustment-Related 

Parameters

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set Value

Input adjustment reset 

(RST)

OFF (0) or ON (1)

(This parameter is used (set to ON) to reset adjusted 

values.)

OFF

Input adjustment point 

LOW (BL)

Scaling span ± 10% (and BL <BH)

SL

Input adjustment LOW 

(AL)

Scaling span ± 10% (and AL <AH)

SL

Input adjustment point 

HIGH (BH)

Scaling span ± 10% (and BL <BH)

SH

Input adjustment HIGH 

(AH)

Scaling span ± 10% (and AL <AH)

SH

10.2 Instrument for Adjustments 

 •

DC voltage/current standard (YOKOGAWA GS200 or equivalent): 1

10.3 Input Adjustment 

10.3.1  Connecting the Adjustment Instrument 

Connect the input and supply voltage as shown in the figure below. 

 

10 11

1 2

3

9

8 7

6 5

4

7
8

N–

L+

(SUPPLY)

R: 100 Ω or 250 Ω, externally connected 

for current input 

Input signal 

Power supply

R

DC voltage/

current 

standard

5
6

+

(IN)

10.3.2  Adjusting Inputs 

Carry out input adjustments between two points, or the low limit (BL: input adjustment point LOW) 

and high limit (BH: input adjustment point HIGH) that have been set within the adjustment range (see 

Section 10.1). 

This subsection describes an example of making an input adjustment between two points, or input 

scaling values “0” and “100” applied at 8 mA input (25% of measured input range) and 16 mA input 

(75% of measured input range) with the MVHK range code No. set to “97,” the measured input range 

set to “4 to 20 mA DC” and the input scaling value (displayed value) set to “-50 to 150.” 

Press              to display 

 

            "LOC."

Press             to display 

"-1." 

The MVHK enters the operable status as soon as the power is turned on, but requires 10 to 15 minutes 

of warm-up to meet the performance requirements. 

When you press the SET/ENT key for more than 3 sec. 

with the Operation Parameter Screen displayed, the Setup 

Parameter Screen 1 appears. 

When the power is turned on, the PV screen of the 

Operation Parameter Screen appears. 

Press this key for 

more than 3 sec.

The decimal point blinks during 

data change.

Press the SET/ENT key to display parameter "LOC." 

Press the DOWN key to display "-1" on the DATA display. 

Press the SET/ENT key to display the Setup Parameter 

Screen 2.

Setup Parameter Screen 1 

Operation Parameter Screen

Power ON

Press            .

Continue to the next page

Summary of Contents for JUXTA MVHK

Page 1: ...O F3 Alarm 1 NO Alarm 2 NC Fail output NO F4 Alarm 1 NC Alarm 2 NC Fail output NO F5 Alarm 1 NO Alarm 2 NO Fail output NC F6 Alarm 1 NC Alarm 2 NO Fail output NC F7 Alarm 1 NO Alarm 2 NC Fail output N...

Page 2: ...UNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage Fail output type 1 PV measured value display Place for adhering the tag number...

Page 3: ...ysteresis of alarm 4 Alarm ON delay OND Sets the condition monitoring time from the establishment of alarm conditions to its output is displayed for MVHK 2 FAIL output type Alarm OFF delay OFD Sets th...

Page 4: ...isplay 1 Continue to the upper right Press the SET ENT key to accept the data as is because the initial value for the range code No 97 is 20 00 The next parameter RL appears because no data has been c...

Page 5: ...play 0 Press Continue to the upper right Press the UP or DOWN key to display 5 on the DATA display Press the SET ENT key to accept alarm 1 hysteresis 5 Press the SET ENT key to display parameter OND T...

Page 6: ...t alarm status red 5 Link to alarm 1 and alarm 2 under normal condition red at alarm status green 6 PV limit when more than PCL less than PCH green when PCL or less PCH or more red 7 PV limit when mor...

Page 7: ...ange code No 97 Measured input range Input scaling value Input range of settings for MVHK range code No 97 Maximum measured input value 20 00 mA Minimum measured input value 4 00 mA Maximum input scal...

Page 8: ...3 2 1 Setting Ranges and Factory Set Values of Monitor Output Communication Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Communication pr...

Reviews: