IM 77J04H31-01E 4th Edition 

Oct. 15, 2019-00

6

Press the SET/ENT key to display parameter "BL."

In this case, the DATA display shows the set minimum 

input scaling value "-50." 
 

Press the UP key to display "0" on the DATA display. 

Press the SET/ENT key to accept this data. 
Press the SET/ENT key to display the next parameter. 

This causes parameter "AL" and the scaling value 

corresponding to the measured value (8 mA) to appear 

alternately. 

Press the UP or DOWN key. 

The decimal point blinks. 

 

Press the SET/ENT key. 

The value before adjustment "2" appears on the DATA 

display. 

Press the SET/ENT key to display the next parameter "BH." 

The decimal point blinks.

The decimal point blinks during 

data change.

Setup Parameter Screen 2

Using the voltage/current standard, apply 8 mA input to the MVHK.

In this case, the DATA display shows the set maximum 

input scaling value "150." 

Press the DOWN key to display "100" on the DATA display. 

Press the SET/ENT key to accept this data. 
Press the SET/ENT key to display the next parameter. 

The decimal point blinks during 

data change. 

Press              to 

 

       display "BL." 

Press             to display 

  "0."

Press             . 

 

Press             .

The measured value and 

parameter AL are 

displayed alternately. 

Press            or             . 

Press             . 

Press             . 

"2" appears on the DATA 

display. 

Press             to display 

 

             "100."

Press             . 
Press             .

The previously adjusted value 

will be reset.

The decimal point blinks during 

data change. 

This causes parameter "AH" and the scaling value 

corresponding to the measured value (16 mA) to appear 

alternately. 

Press the UP or DOWN key. 

 

The decimal point blinks. 

 

Press the SET/ENT key. 

The value before adjustment "99" appears on the DATA 

display. 

This completes the input adjustment for the MVHK. 

Press the SET/ENT key to display parameter "RST." 

Press the UP key to display "ON" on the DATA display. 

Press the SET/ENT key.

This resets the previously adjusted value.

Setup Parameter Screen 2

Using the voltage/current standard, apply 16 mA input to the 

MVHK.

If additional re-adjustment must be made, take the following steps and then perform the 

procedure above. 

Press               to display 

"RST." 

Press             to display 

"ON."

Press            .

This completes the input 

adjustment.

The decimal point blinks.

The measured value and 

parameter AH are displayed 

alternately.

Press              or             .

Press             . 

11.  SETTING ACTIVE COLOR PV DISPLAY (PV DISPLAY COLOR 

CHANGING FUNCTION)

11.1 Setting Ranges and Factory-Set Values 

Setup Parameter Screen 1

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set Value

High limit for PV display 

color change (PCH)

When PV display color mode (PCM) is 6 or 7: 

PCL+1digit to 9999

When PV display color mode (PCM) is 8 or 9: 

 

-100.0 to 100.0% of the measured input range

*  The setting range depends on the setting of the 

decimal point position (SDP).

Low limit for PV display 

color change (PCL)

When PV display color mode (PCM) is 6 or 7: 

 

-1999 to PCH-1digit

When PV display color mode (PCM) is 8 or 9: 

 

-100.0 to 100.0% of the measured input range

*  The setting range depends on the setting of the 

decimal point position (SDP).

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set Value

PV display color mode 

(PCM)

0: Fixed in green 

 

1: Fixed in red

2:  Link to alarm 1 

 

(under normal condition: green; at alarm status: red)

3:  Link to alarm 1  

(under normal condition: red; at alarm status: green)

4:  Link to alarm 1 and alarm 2 

 

(under normal condition: green; at alarm status: red)

5:  Link to alarm 1 and alarm 2 

 

(under normal condition: red; at alarm status: green)

6:  PV limit* 

 

(when more than PCL, less than PCH: green; when 

PCL or less, PCH or more: red)

7:  PV limit*  

(when more than PCL, less than PCH:red; when 

PCL or less, PCH or more: green)

8:  SP deviation* 

 

(when more than SP-PCL, less than SP+PCH: 

green; when SP-PCL or less, SP+PCH or more: red)

9:  SP deviation* 

 

(when more than SP-PCL, less than SP+PCH: red; 

when SP-PCL or less, SP+PCH or more: green)

10:  Link to alarm 1 to alarm 4  

(under normal condition: green; at alarm status: 

red)

11:  Link to alarm 1 to alarm 4  

(under normal condition: red; at alarm status: 

green)

1

*:  

PV display color is changed linking to the setting range of high limit (PCH) and low limit (PCL) for PV display 

color change.

11.2 Setting Active Color PV Display

This section describes an example of setting the PV display color mode (PCM) to “6,” high limit for 

PV display color change (PCH) to “70” and low limit (PCL) to “20.” 

The procedure below begins with the condition in which the Setup Parameter Screen 2 is displayed.

When you press the SET/ENT key for more than 3 sec. 

with the Operation Parameter Screen displayed, the Setup 

Parameter Screen 1 appears.

Press the SET/ENT key to display parameter "PCH."

Press the UP or DOWN key to display "70" on the DATA 

display.

Press this key for 

more than 3 sec. 

The decimal point blinks during 

data change. 

Operation Parameter Screen 

This completes the process for 

setting the high limit for PV display

color change.

Press               to display 

 

    "PCH." 

Press             or               
to display  "70."

"

Press              .

Press              to display

                             "PCL."     

Press the SET/ENT key to accept the high limit for PV 

display color change "70." 

Press the SET/ENT key to display parameter "PCL." 

Press the UP or DOWN key to display "20" on the DATA 

display.

The decimal point blinks during 

data change. 

This completes the process for 

setting the low limit for PV display

color change.

Press             or               
to display  "20."

Press              .

Press              for more

                           than 3 sec.     

Press the SET/ENT key to accept the low limit for PV 

display color change "20." 

Press the SET/ENT key for more than 3 sec.

This causes the Operation Parameter Screen to appear.

Press the SET/ENT key to display parameter "PCM."

Press the UP or DOWN key to display "6" on the DATA 

display.

The decimal point blinks during 

data change. 

This completes the process for 

setting the PV display color mode.

Press               to display 

 

    "PCM." 

Press             or               
to display  "6."

Press              .

Press              for more

                           than 3 sec. 

Press the SET/ENT key to accept PV display color 

mode "6." 

Press the SET/ENT key for more than 3 sec.

This causes the Operation Parameter Screen to appear.

Setting the PV display color mode

Setting the high and low limits for PV display color change

Setup Parameter Screen 1 

Setup Parameter Screen 2 

To the Operation Parameter Screen

 

12.  OTHER PARAMETERS 

12.1 Setting Ranges and Factory-Set Values 

Setup Parameter Screen 1

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

Key lock (LOC)

  0: Without lock. All parameters can be set.

  1: Parameters other than the operation  

parameters cannot be changed.

  2: All parameters cannot be changed.

 -1: This moves to the Setup Parameter Screen 2.

0

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

Measured input bias (BS) -1999 to 9999

0

Economical mode time 

(ECO)

0 (Continuous: no display OFF function), 1 to 60 

(minutes)

10

Relay specification 

display (RLY)

You can check the relay specifications for alarm output 

1, alarm output 2, and FAIL output.

 

The setting cannot be changed only by checking.

-----

Summary of Contents for JUXTA MVHK

Page 1: ...O F3 Alarm 1 NO Alarm 2 NC Fail output NO F4 Alarm 1 NC Alarm 2 NC Fail output NO F5 Alarm 1 NO Alarm 2 NO Fail output NC F6 Alarm 1 NC Alarm 2 NO Fail output NC F7 Alarm 1 NO Alarm 2 NC Fail output N...

Page 2: ...UNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage Fail output type 1 PV measured value display Place for adhering the tag number...

Page 3: ...ysteresis of alarm 4 Alarm ON delay OND Sets the condition monitoring time from the establishment of alarm conditions to its output is displayed for MVHK 2 FAIL output type Alarm OFF delay OFD Sets th...

Page 4: ...isplay 1 Continue to the upper right Press the SET ENT key to accept the data as is because the initial value for the range code No 97 is 20 00 The next parameter RL appears because no data has been c...

Page 5: ...play 0 Press Continue to the upper right Press the UP or DOWN key to display 5 on the DATA display Press the SET ENT key to accept alarm 1 hysteresis 5 Press the SET ENT key to display parameter OND T...

Page 6: ...t alarm status red 5 Link to alarm 1 and alarm 2 under normal condition red at alarm status green 6 PV limit when more than PCL less than PCH green when PCL or less PCH or more red 7 PV limit when mor...

Page 7: ...ange code No 97 Measured input range Input scaling value Input range of settings for MVHK range code No 97 Maximum measured input value 20 00 mA Minimum measured input value 4 00 mA Maximum input scal...

Page 8: ...3 2 1 Setting Ranges and Factory Set Values of Monitor Output Communication Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Communication pr...

Reviews: