IM 77J04H31-01E 4th Edition 

Oct. 15, 2019-00

7

12.2 Setting Key Lock 

This section describes an example of locking keys so that parameter settings other than the 

operation parameters cannot be changed. The procedure below begins with the condition in which 

the Setup Parameter Screen 1 is displayed. 

Press the SET/ENT key to display parameter "LOC." 

Press the UP key to display "1" on the DATA display. 

Press the SET/ENT key to accept this data.

The decimal point blinks during 

data change.

Setup Parameter Screen 1

Press               to display 

  

"LOC." 

Press             to display 

  

"1." 

Press             .

12.3 Setting Economical Mode Time

Setting economical mode time allows indications on the PV display to be extinguished if no keystroke 

is made within the set time. 

The MVHK’s power consumption in the OFF mode is approximately 0.5 W or 1 VA during normal 

operations (non-alarm status). This section describes an example of setting the economical mode 

time to “5 minutes” (factory-set value: 10 minutes ).

The procedure below begins with the condition in which the Setup Parameter Screen 2 is displayed. 

Press the SET/ENT key to display parameter "ECO." 

Press the DOWN key to display "5" on the DATA display. 

Press the SET/ENT key to accept this data.

The decimal point blinks during 

data change.

Setup Parameter Screen 2

Press              to display 

 "ECO." 

Press              to display 

 "5."

 

Press              . 

 CAUTION 

The economical mode is temporarily released at the time of PV display color change 

and the PV display lights up. After the set economical mode time elapsed from the time 

of returning to normal operation, the economical mode operation begins again.

12.4 Setting Input Bias 

This section describes an example of correcting an error by setting input bias if there is an error of 

“-1” in the MVHK scaling value (displayed value) with respect to the measured value. The procedure 

below begins with the condition in which the Setup Parameter Screen 2 is displayed. 

Press the SET/ENT key to display parameter "BS." 

Press the UP key to display "1" on the DATA display. 

Press the SET/ENT key to accept this data. 

The decimal point blinks during 

data change. 

Setup Parameter Screen 2 

Press               to display 

 "BS." 

Press              to display 

                                  "1."

Press              . 

12.5 

Confirmation of relay contact specifications (FAIL output type only)

For the FAIL output type (type code 2), you can check the relay contact specifications of alarm output 

1, alarm output 2, and FAIL output specified at the time of order. The setting cannot be changed 

only by checking. This section describes the case of MVHK option specification code “/ F3”. The 

procedure below begins with the condition in which the Setup Parameter Screen 2 is displayed.

Press               to display 

 "RLY." 

Press the SET/ENT key to display parameter "RLY." 

Displays the status of relay contact specifications on the 

DATA display.

From left, alarm output 1, alarm output 2, off, and FAIL 

output. 

Setup Parameter Screen 2 

: NO (a-contact)

FAIL output: NO

Alarm output 2: NC

Alarm output 1: NO

: NC (b-contact)

13.  MONITOR OUTPUT 

13.1 Monitor Output (Analog) 

Monitor output (analog) is added only when monitor output code “6” or “A” is specified at the time of 

order. 

13.1.1  Setting Monitor Output 

In setting monitor output, the maximum monitor output value (RTH) and minimum monitor output 

value (RTL) can be freely set within the range of the maximum input scaling value (SH) and minimum 

input scaling value (SL) that have been set for the MVHK. 

For example, when the MVHK range code No. (IN) is “97,” the measured input range (RL, RH) is 

“4 to 20 mA DC,” the input scaling values (displayed values) (SL, SH) are “-50 to 150” and monitor 

output is “1 to 5 V DC,” setting the maximum monitor output value (RTH) to “125” and the minimum 

monitor output value (RTL) to “-25” causes monitor output to be “1 V” when input to the MVHK is 6 

mA (scaling value -25) as shown below. 

 

0 mA

1 V

4 mA

(RL) 6 mA

18 mA

20 mA

5 V

20 mA

(RH)

-50

(SL)

-25

(RTL)

150

(SH)

125

(RTH)

Range code No. 97

Measured input range

 

Input scaling value

Input range of settings for 

MVHK range code No. 97

Maximum measured input value:

  20.00 mA 

Minimum measured input value:

  4.00 mA

Maximum input scaling value: 150 

Minimum input scaling value: -50

Monitor output setting

Maximum monitor output value: 125 

Minimum monitor output value: -25

Monitor output range

Fixed to 4 to 20 mA or 1 to 5 V DC

(5 V is output when the input scaling value is 125, 

while 1 V is output when it is -25.) 

13.1.2   Setting Ranges and Factory-Set Values of Monitor Output (Analog)-Related 

Parameters 

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

Maximum monitor output 

value (RTH)

RTL + 1 digit to 9999

Within the instrument input range

SH

Minimum monitor output 

value (RTL)

-1999 to RTH - 1 digit

Within the instrument input range

SL

Visibility of monitor 

output adjustment screen 

(MON)

OFF (invisible) or ON (visible)

Set this parameter to "ON" for adjustments of monitor 

output.

OFF

(invisible)

Forced output of a 

monitor output value 

(MAN)

-25.0 to +125.0 (%)

Note that the assured range is -6.0 to +106 (%).

0.0

Monitor output zero 

adjustment (ZER)

-19.99 to 20.00 (%)

0.00

Monitor output span 

adjustment (SPN)

-19.99 to 20.00 (%)

0.00

13.1.3  Setting Monitor Output 

 CAUTION 

Accuracy (±0.1% of output span) is limited depending on the settings for input scaling 

and maximum and minimum monitor output values. For more information on accuracy 

limitations, refer to the general specifications (GS 77J04H31-01E). 

This subsection describes an example of setting the maximum monitor output value (RTH) to “125” 

and minimum monitor output value (RTL) to “-25” when the MVHK input scaling values (displayed 

values) (SL, SH) are “-50 to 150.”

When you press the SET/ENT key for more than 3 sec. 

with the Operation Parameter Screen displayed, the Setup 

Parameter Screen 1 appears. 

When the power is turned on, the PV screen of the 

Operation Parameter Screen appears. 

Press the SET/ENT key to display parameter "RTH."

In this case, the DATA display shows the set maximum 

input scaling value "150." 
 

Press the DOWN key to display "125" on the DATA display. 

Press the SET/ENT key to accept this data. 

Press the SET/ENT key to display the next parameter. 

Press this key for 

more than 3 sec. 

The decimal point blinks during 

data change.

The decimal point blinks during 

data change.

Press the SET/ENT key to display parameter "LOC." 

Press the DOWN key to display "-1" on the DATA display. 

Press the SET/ENT key to display the Setup Parameter 

Screen 2.

Press the SET/ENT key to display parameter "RTL."

In this case, the DATA display shows the set minimum 

input scaling value "-50." 
 

Press the UP key to display "-25" on the DATA display. 

Press the SET/ENT key to accept this data. 

The decimal point blinks during 

data change.

Setup Parameter Screen 1 

Setup Parameter Screen 2

Operation Parameter Screen

Power ON 

This completes the procedure 

for setting the maximum 

monitor output value. 

This completes the procedure 

for setting the minimum monitor 

output value. 

Press               to display 

 "LOC." 

Press              to display 

 "-1." 
 

Press              .

Press              to display 

 "RTL." 

 

Press             to display 

 "-25."

 

Press             . 

Press              to display 

 "RTH." 

 

Press             to display 

 "125."

 
 

Press             . 

 
Press             . 

13.1.4  Adjusting Monitor Output 

(1) Instruments for adjustment 

 •

Digital multimeter (DMM) (YOKOGAWA DM7560 or the equivalent): 1

 •

Precision resistor of 250 Ω ± 0.01%, 0.25 W or more: 1

(2) Output adjustments 

Connect each instrument as shown below. 

10 11

1 2

3

9

8 7

6 5

4

7
8

N–

L+

(SUPPLY)

Power supply

R: 250 Ω precision resistor for current 

output

R

DMM

Main unit

Socket

+

1

1
3

3

Monitor output 

(3) Adjusting monitor output 

  The following describes an example of adjusting an error when the minimum monitor output value 

(measured value) is 1.008 V (an error of 0.008 V) with the MVHK monitor output set to “1 to 5 V 

DC.” The basic adjusting procedure for the maximum monitor output value is the same as that of 

the minimum monitor output value; perform it by referring to the procedure below. 

  The procedure below begins with the condition in which the Setup Parameter Screen 2 is 

displayed. 

Summary of Contents for JUXTA MVHK

Page 1: ...O F3 Alarm 1 NO Alarm 2 NC Fail output NO F4 Alarm 1 NC Alarm 2 NC Fail output NO F5 Alarm 1 NO Alarm 2 NO Fail output NC F6 Alarm 1 NC Alarm 2 NO Fail output NC F7 Alarm 1 NO Alarm 2 NC Fail output N...

Page 2: ...UNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage Fail output type 1 PV measured value display Place for adhering the tag number...

Page 3: ...ysteresis of alarm 4 Alarm ON delay OND Sets the condition monitoring time from the establishment of alarm conditions to its output is displayed for MVHK 2 FAIL output type Alarm OFF delay OFD Sets th...

Page 4: ...isplay 1 Continue to the upper right Press the SET ENT key to accept the data as is because the initial value for the range code No 97 is 20 00 The next parameter RL appears because no data has been c...

Page 5: ...play 0 Press Continue to the upper right Press the UP or DOWN key to display 5 on the DATA display Press the SET ENT key to accept alarm 1 hysteresis 5 Press the SET ENT key to display parameter OND T...

Page 6: ...t alarm status red 5 Link to alarm 1 and alarm 2 under normal condition red at alarm status green 6 PV limit when more than PCL less than PCH green when PCL or less PCH or more red 7 PV limit when mor...

Page 7: ...ange code No 97 Measured input range Input scaling value Input range of settings for MVHK range code No 97 Maximum measured input value 20 00 mA Minimum measured input value 4 00 mA Maximum input scal...

Page 8: ...3 2 1 Setting Ranges and Factory Set Values of Monitor Output Communication Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Communication pr...

Reviews: