3-10
TI04L55B01-01EN
Internal Memory
The recorded measurement data is divided at a specific time interval (data length for event data
and file save interval for display data) and saved to files.
If the internal memory is full or if the number of display data files and event data files exceeds 500
for the GM10-1 or 1000 for the GM10-2, files are overwritten from the oldest file.
File 1
File 2
File 3
File 4
Update date
Internal memory
Old
New
Data length (Event data)
File saving interval (Display data)
Overwrite
Time
File
• • •
Recording Channels
Set the channels for recording the measurement data of event data, display data, and manual
sampled data.
Only the channels assigned to recording channels are recorded as measurement data.
You can select the channels to record from AI channels, DI channels, pulse input channels, DO
channels, math channels (/MT option), and communication channels (/MC option).
Input/output
channel
Communication
channel
Math channel
Record channel
C001
C002
C003
A001
A002
A003
0001
0003
0002
Record
0001
0003
0004
0005
C004
C005
A004
A005
0002
A001
A004
A005
C002
C004
Number of recording channels
Data Type
Maximum Number of Recording Channels
GM10-1
GM10-2
Event data
500ch (250ch)*
1000ch (600ch)*
Displat data
500ch (250ch)*
1000ch (600ch)*
Manual sampling data
50ch
100ch
* Numbers in parentheses are for when the measurement mode is set to Dual interval.
The maximum number of channels that the GM can record varies depending on the recording
interval and recording data type (for the GM10-2).
Summary of Contents for SMARTDAC+ GM