3-30
TI04L55B01-01EN
3.2.10
Fail, Status Output
CPU errors (FAIL) and status can be output as relay signals.
You can select which status to output from event action.
To output relay signals, you need a digital output module (GX90YD) or digital input/output module
(GX90WD).
Status Output Item
Device information
Description
Details
Device status
Recording
A relay signal is output when
recording starts.
------
Math
A relay signal is output when
computation starts.
------
User lock out
A relay signal is output when a
user lockout occurs.
------
Memory/media error
A relay signal is output when
an error occurs in the internal
memory or external storage
medium.
Error in the internal memory.
Error in the external storage
media.
Measurement error
A relay signal is output when a
measurement error occurs.
Error in the A/D converter.
A burnout was detected.
This occurs when
thermocouple or RTD wires
are disconnected or when
general signals are outside the
specifications.
Module error was detected.
Communication
error
A relay signal is output when a
communication error occurs.
A communication error
occurred in the Modbus
master, Modbus client, WT
communication (/E2 option),
or SLMP communication (/E4
option).
Alarm
A relay signal is output when an
alarm occurs. However, alarms
that are set not to display their
occurrence are not output to the
relay.
------
Summary of Contents for SMARTDAC+ GM