(1) GM-10 Firmware Update.
Preparation
●
Copy all the required files /folder to the root directory of the SD card. This
should consist of a folder named SYSTEM and (3) files,
ndacSV_2_main.rom, ndacSV_boot.rom, and ndacSV_main.rom.
Insert the SD card
●
Power on the GM while pressing START key.
●
Once the procedure is completed, there will be disparity between firmware
of the main unit and the firmware of the modules and this will cause error.
●
The following error message will be shown alternately in the GM.
E5 , 59
This indicates completion of the procedure to update the main GM10 unit.