(1) Preparation
To configure the network shown in figure 1, prepare the hardware and configuration software listed in table 1.
First, in order to configure the field wireless network and Modbus communication, decide on the network ID (group
number of the devices to connect wirelessly), the device tag of the field wireless device (YTMX580), network parameters
for the Ethernet connection, and so on. In this guide, the connection setup example shown in table 3 will be configured.
Item before change
GX20W
Built-in GW
YTMX580
Configuration PC
Network ID
2 to 65535
—
100
1
—
EUI64
Unique to each device
—
Device-specific value Device-specific value
—
Device tag
For each device (up to 16 characters)
—
YFGW-GW001
Not set
—
Ethernet parameter
IP Address
192.168.200.100 192.168.200.200
—
—
Subnet Mask
255.255.255.0
255.255.255.0
—
—
Default Gateway
192.168.200.253 192.168.200.253
—
—
Join Key
Shared by GW and YTMX (32 characters) —
Not set
Not set
—
Modbus register
Register map assignment
Not set
Not set
—
—
indicates factory default value.
indicates not changeable.
Item after change
GX20W
Built-in GW
YTMX580
Configuration PC
Network ID
2 to 65535
—
100
100
—
EUI64
EUI64 for each device
—
Device-specific value Device-specific value
—
Device tag
For each device (up to 16 characters)
—
YFGW-GW001
YTMX-TEST01
—
Ethernet parameter
IP Address
192.168.200.100 192.168.200.200
—
192.168.200.101
Subnet Mask
255.255.255.0
255.255.255.0
—
255.255.255.0
Default Gateway
192.168.200.253 192.168.200.253
—
192.168.200.253
Join Key
Shared by GW and YTMX (32 characters) —
[C0 C1 C2 C3 C4 C5 C6 C7 C8 C9 CA CB
CC CD CE CF]*
—
Modbus register
Register map assignment
See step (9)
Display settings.
See step (6) Creating
a project.
—
—
indicates no change from factory default setting.
indicates a value changed from its factory default.
indicates not changeable.
* Join Key is a unique value assigned automatically by the configuration software and cannot be viewed.
Table 3 Connection setup example
(2) Provisioning
Provision the YTMX580.
Prepare a configuration PC, YTMX580, and infrared
adapter as shown in figure 1.
For the preparation procedure of FieldMate (use the
Provisioning Device Tool for R2.06.00) and infrared
adapter, see the relevant manuals.
The provisioning procedure is described in steps
to
.
Start FieldMate.
Select the ISA100(Infrared) option, and check
that the a COM port is displayed for the applicable
ISA100(Infrared). If it is not displayed, click Setting, and
select the port that the infrared adapter is connected to.
Point the infrared adapter to the YTMX580 infrared
port, and click Login (figure 4).
The Ethernet parameters on the configuration PC must
be set in order for it to connect to the GX20W via Ethernet
and configure the GX20W. Table 4 lists the configuration
tools and the like used in this guide. Install the software
tools in the configuration PC.
Tool Name
Manufacturer Revision
Remarks
Infrared adapter driver
IR224UN
ACTiSYS
—
Supplied with the
infrared adapter
FieldMate
Yokogawa
Electric
Corporation
R2.06.00 or
later
F9197DS, sold
separately
FieldMate Provisioning
Device Tool
Yokogawa
Electric
Corporation
—
R2.06.00 is
supplied with
FieldMate
Field Wireless
Configurator
Yokogawa
Electric
Corporation
R1.02.01 or
later
GX20W
accompanying
DVD-ROM
Field Wireless
Management Tool
Yokogawa
Electric
Corporation
R1.02.00 or
later
GX20W
accompanying
DVD-ROM
CF/DD Files(for
YTMX580)
Yokogawa
Electric
Corporation
0018 or later Number:0x1802
GX20W
accompanying
DVD-ROM
Communication DTM for
YFGW710
Yokogawa
Electric
Corporation
1.01.00 or
later
GX20W
accompanying
DVD-ROM
DeviceDTM for YTA
(YTA ISA100 DTM)
Yokogawa
Electric
Corporation
3.1.1.48
GX20W
accompanying
DVD-ROM
Table 4 Software used